Schneider Electric

Schneider Electric LC1D115F7 IEC contactor, TeSys Deca, nonreversing, 115A, 75HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D115F7
MPN:
LC1D115F7
Condition:
New
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Contactor Application:
resistive load || motor control
Control Circuit Voltage Limits:
0.3...0.5 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55°C operational AC 50/60 Hz || 1...1.15 Uc 55-70°C operational AC 50/60 Hz
Protective Cover:
with
Circularity Profile:
ENVEOLI100405EN
Environmental Disclosure:
ENVPEP060301EN
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Operating Time:
6...20 ms opening || 20...50 ms closing
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Safety Reliability Level:
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Protective Treatment:
THIEC 60068-2-30
Product Certifications:
UL || CSA || CCC || UKCA || CE || EAC || Marine
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
Eu Rohs Directive:
Compliant with Exemptions
Insulation Resistance:
> 10 MOhm for Signaling circuit
Inrush Power In Va:
280-350 VA 60 Hz cos phi 0.8 (at 20°C) || 280-350 VA 50 Hz cos phi 0.8 (at 20°C)
Electrical Durability:
0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Product Or Component Type:
contactor
Heat Dissipation:
3-8 W at 50/60 Hz
Rohs Exemption Information:
Yes
Sustainable Offer Status:
Green Premium product
Mounting Support:
rail || plate
Range Of Product:
TeSys Deca
Weight:
2.5 kg
Net Weight:
2.5 kg
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Maximum Operating Rate:
2400 cyc/h 60°C
Pollution Degree:
3
Width:
120 mm
Motor Power Kw:
30 kW at 220...230 V AC 50/60 Hz (AC-3) || 55 kW at 380...400 V AC 50/60 Hz (AC-3) || 59 kW at 415...440 V AC 50/60 Hz (AC-3) || 75 kW at 500 V AC 50/60 Hz (AC-3) || 80 kW at 660...690 V AC 50/60 Hz (AC-3) || 65 kW at 1000 V AC 50/60 Hz (AC-3) || 18.
Hold-In Power Consumption In Va:
2-18 VA 60 Hz cos phi 0.3 (at 20°C) || 2-18 VA 50 Hz cos phi 0.3 (at 20°C)
[Icw] Rated Short-Time Withstand Current:
250 A 40°C - 10 min for power circuit || 550 A 40°C - 1 min for power circuit || 950 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Fire Resistance:
850°C IEC 60695-2-1
Range:
TeSys
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Depth:
136 mm
Operating Altitude:
0...9842.52 ft (0...3000 m)
Compatibility Code:
LC1D
Maximum Horse Power Rating:
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Pole Contact Composition:
3 NO
Control Circuit Type:
AC 50/60 Hz standard
Auxiliary Contact Composition:
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current:
200 A (at 60°C) for power circuit
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Utilisation Category:
AC-3 || AC-4 || AC-1 || AC-3e
Height:
158 mm
Power Dissipation Per Pole:
24 W AC-1 || 7.9 W AC-3 || 7.9 W AC-3e
$479.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with a 600VAC up to 250A circuit breaker, this contactor can have a SCCR up to 50kA. When used with 600VAC Class J or CC fuses up to 250A, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose