Schneider Electric

Schneider Electric LC1D115N7 IEC contactor, TeSys Deca, nonreversing, 115A, 75HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 415VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D115N7
MPN:
LC1D115N7
Condition:
New
Electrical Durability:
0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
Overvoltage Category:
III
Associated Fuse Rating:
250 A gG at <= 690 V coordination type 1 for power circuit || 200 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for Signaling circuit
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Minimum Switching Current:
5 mA for Signaling circuit
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² -
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Environmental Disclosure:
ENVPEP060301EN
Maximum Horse Power Rating:
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Heat Dissipation:
3-8 W at 50/60 Hz
Signaling Circuit Frequency:
25...400 Hz
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || IEC 60947-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Power Dissipation Per Pole:
24 W AC-1 || 7.9 W AC-3 || 7.9 W AC-3e
Pollution Degree:
3
Mounting Support:
rail || plate
Motor Power Kw:
30 kW at 220...230 V AC 50/60 Hz (AC-3) || 55 kW at 380...400 V AC 50/60 Hz (AC-3) || 59 kW at 415...440 V AC 50/60 Hz (AC-3) || 75 kW at 500 V AC 50/60 Hz (AC-3) || 80 kW at 660...690 V AC 50/60 Hz (AC-3) || 65 kW at 1000 V AC 50/60 Hz (AC-3) || 18.
Utilisation Category:
AC-4 || AC-3 || AC-1 || AC-3e
Control Circuit Voltage Limits:
0.3...0.5 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55°C operational AC 50/60 Hz || 1...1.15 Uc 55-70°C operational AC 50/60 Hz
Operating Altitude:
0...9842.52 ft (0...3000 m)
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Fire Resistance:
850°C IEC 60695-2-1
Mercury Free:
Yes
Mechanical Durability:
8 Mcycles
Ip Degree Of Protection:
IP20 front face IEC 60529
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Eu Rohs Directive:
Compliant with Exemptions
[Ue] Rated Operational Voltage:
power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility Code:
LC1D
Operating Time:
6...20 ms opening || 20...50 ms closing
Range:
TeSys
Hold-In Power Consumption In Va:
2-18 VA 60 Hz cos phi 0.3 (at 20°C) || 2-18 VA 50 Hz cos phi 0.3 (at 20°C)
Irms Rated Making Capacity:
1260 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Pole Contact Composition:
3 NO
Range Of Product:
TeSys Deca
Minimum Switching Voltage:
17 V for Signaling circuit
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Warranty:
18 months
Flame Retardance:
V1 conforming to UL 94
Rohs Exemption Information:
Yes
Insulation Resistance:
> 10 MOhm for Signaling circuit
Contactor Application:
motor control || resistive load
Pvc Free:
Yes
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
[Uc] Control Circuit Voltage:
415 V AC 50/60 Hz
Coil Technology:
built-in bidirectional peak limiting diode suppressor
$479.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with a 600VAC up to 250A circuit breaker, this contactor can have a SCCR up to 50kA. When used with 600VAC Class J or CC fuses up to 250A, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 415 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose