Schneider Electric

Schneider Electric LC1D115U7 IEC contactor, TeSys Deca, nonreversing, 115A, 75HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 240VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D115U7
MPN:
LC1D115U7
Condition:
New
Fire Resistance:
850°C IEC 60695-2-1
Overvoltage Category:
III
Ip Degree Of Protection:
IP20 front face IEC 60529
Protective Treatment:
THIEC 60068-2-30
[Ith] Conventional Free Air Thermal Current:
200 A (at 60°C) for power circuit
Average Impedance:
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Heat Dissipation:
3-8 W at 50/60 Hz
Country of Origin:
Mexico
Depth:
136 mm
Circularity Profile:
ENVEOLI100405EN
Mechanical Durability:
8 Mcycles
Associated Fuse Rating:
250 A gG at <= 690 V coordination type 1 for power circuit || 200 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for Signaling circuit
[Ue] Rated Operational Voltage:
power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
Sustainable Offer Status:
Green Premium product
Pvc Free:
Yes
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Maximum Horse Power Rating:
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Net Weight:
2.5 kg
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Ie] Rated Operational Current:
200 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² -
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Environmental Disclosure:
ENVPEP060301EN
Protective Cover:
with
Operating Altitude:
0...9842.52 ft (0...3000 m)
Eu Rohs Directive:
Compliant with Exemptions
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Control Circuit Voltage Limits:
0.3...0.5 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55°C operational AC 50/60 Hz || 1...1.15 Uc 55-70°C operational AC 50/60 Hz
Motor Power Kw:
30 kW at 220...230 V AC 50/60 Hz (AC-3) || 55 kW at 380...400 V AC 50/60 Hz (AC-3) || 59 kW at 415...440 V AC 50/60 Hz (AC-3) || 75 kW at 500 V AC 50/60 Hz (AC-3) || 80 kW at 660...690 V AC 50/60 Hz (AC-3) || 65 kW at 1000 V AC 50/60 Hz (AC-3) || 18.
Sustainable Packaging:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mercury Free:
Yes
[Icw] Rated Short-Time Withstand Current:
250 A 40°C - 10 min for power circuit || 550 A 40°C - 1 min for power circuit || 950 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Tightening Torque:
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Width:
120 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Range:
TeSys
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || IEC 60947-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Maximum Operating Rate:
2400 cyc/h 60°C
Product Or Component Type:
contactor
Irms Rated Making Capacity:
1260 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Electrical Durability:
0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
[Uc] Control Circuit Voltage:
240 V AC 50/60 Hz
Pollution Degree:
3
Device Short Name:
LC1D
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Range Of Product:
TeSys Deca
Compatibility Code:
LC1D
$479.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with a 600VAC up to 250A circuit breaker, this contactor can have a SCCR up to 50kA. When used with 600VAC Class J or CC fuses up to 250A, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 240 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose