Control Circuit Voltage Limits:
0.3...0.5 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55°C operational AC 50/60 Hz || 1...1.15 Uc 55-70°C operational AC 50/60 Hz
[Ie] Rated Operational Current:
200 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Flame Retardance:
V1 conforming to UL 94
Net Weight:
2.5 kg
[Ith] Conventional Free Air Thermal Current:
200 A (at 60°C) for power circuit
Compatibility Code:
LC1D
Safety Reliability Level:
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree:
3
Sustainable Offer Status:
Green Premium product
Circularity Profile:
ENVEOLI100405EN
Product Or Component Type:
contactor
Hold-In Power Consumption In Va:
2-18 VA 60 Hz cos phi 0.3 (at 20°C) || 2-18 VA 50 Hz cos phi 0.3 (at 20°C)
Associated Fuse Rating:
250 A gG at <= 690 V coordination type 1 for power circuit || 200 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for Signaling circuit
Rohs Exemption Information:
Yes
Product Certifications:
UL || CSA || CCC || UKCA || CE || EAC || Marine
Pvc Free:
Yes
Minimum Switching Voltage:
17 V for Signaling circuit
Mercury Free:
Yes
Control Circuit Type:
AC 50/60 Hz standard
Country of Origin:
Czechia
Overvoltage Category:
III
Maximum Horse Power Rating:
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Eu Rohs Directive:
Compliant with Exemptions
Mechanical Durability:
8 Mcycles
Sustainable Packaging:
Yes
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
Operating Altitude:
0...9842.52 ft (0...3000 m)
Motor Power Kw:
30 kW at 220...230 V AC 50/60 Hz (AC-3) || 55 kW at 380...400 V AC 50/60 Hz (AC-3) || 59 kW at 415...440 V AC 50/60 Hz (AC-3) || 75 kW at 500 V AC 50/60 Hz (AC-3) || 80 kW at 660...690 V AC 50/60 Hz (AC-3) || 65 kW at 1000 V AC 50/60 Hz (AC-3) || 18.
Weight:
2.5 kg
Device Short Name:
LC1D
Irms Rated Making Capacity:
1260 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Environmental Disclosure:
ENVPEP060301EN
Heat Dissipation:
3-8 W at 50/60 Hz
[Icw] Rated Short-Time Withstand Current:
250 A 40°C - 10 min for power circuit || 550 A 40°C - 1 min for power circuit || 950 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Warranty:
18 months
Pole Contact Composition:
3 NO
Maximum Operating Rate:
2400 cyc/h 60°C
Protective Treatment:
THIEC 60068-2-30
Average Impedance:
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Mounting Support:
rail || plate
Poles Description:
3P
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Protective Cover:
with
$479.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with a 600VAC up to 250A circuit breaker, this contactor can have a SCCR up to 50kA. When used with 600VAC Class J or CC fuses up to 250A, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 400 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.