Schneider Electric

Schneider Electric LC1D126BLS207 IEC contactor, TeSys D, nonreversing, 12A, 7.5HP at 480VAC, 3 phase, 3 pole, 3 NO, low consumption 24 VDC coil, open

(No reviews yet) Write a Review
SKU:
LC1D126BLS207
MPN:
LC1D126BLS207
Condition:
New
Sustainable Offer Status:
Green Premium product
Product Or Component Type:
contactor
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Environmental Disclosure:
ENVPEP2205004
Circularity Profile:
N/A
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Fire Resistance:
850°C IEC 60695-2-1
Protective Cover:
with
Inrush Power In W:
4-4 W 20°C)
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Pvc Free:
Yes
Power Dissipation Per Pole:
1.56 W AC-1 || 0.36 W AC-3 || 0.36 W AC-3e
Overvoltage Category:
III
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Device Short Name:
LC1D
Auxiliary Contact Composition:
1 NO + 1 NC
Country of Origin:
France
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Mercury Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Depth:
95 mm
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Contactor Application:
motor control || resistive load
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Poles Description:
3P
Coil Technology:
with integral suppression device
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Operating Time:
77±15 % ms closing || 25±20 % ms opening
Height:
77 mm
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || EN 45545: R22 HL3 || EN 45545: R26 HL3 || DIN 5510-2
Mounting Support:
rail || plate
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Net Weight:
0.325 kg
Pole Contact Composition:
3 NO
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-70°C operational DC
Insulation Resistance:
> 10 MOhm for Signaling circuit
Range:
TeSys || TeSys Deca
Eu Rohs Directive:
Compliant with Exemptions
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Control Circuit Type:
DC low consumption
Compatibility Code:
LC1D
Electrical Durability:
2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 12 A AC-3e <= 440 V
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
Minimum Switching Current:
5 mA for Signaling circuit
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3
$187.68

Description

This TeSys D contactor has been designed for motor control in railway applications. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200 to 208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.07 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product. Contactor is also compliant with the railway European standard EN 45545 R22HL3.