Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Range Of Product:
TeSys Deca
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 8 mm
Electrical Durability:
2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 12 A AC-3e <= 440 V
Heat Dissipation:
2-3 W at 50/60 Hz
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
Fire Resistance:
850°C IEC 60695-2-1
Flame Retardance:
V1 conforming to UL 94
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Warranty:
18 months
Eu Rohs Directive:
Compliant
Pvc Free:
Yes
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Weight:
0.325 kg
Protective Cover:
with
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Circularity Profile:
ENVEOLI1501004
Signaling Circuit Frequency:
25...400 Hz
Mechanical Durability:
15 Mcycles
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Maximum Operating Rate:
3600 cyc/h 60°C
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Product Or Component Type:
contactor
Pole Contact Composition:
3 NO
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Net Weight:
0.325 kg
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals flat Ø 8 mm M3.5 || power circuit 1.7 N.m lugs-ring terminals Philips No 2 M3
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
Environmental Disclosure:
ENVPEP1501004
Poles Description:
3P
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Operating Time:
12...22 ms closing || 4...19 ms opening
Control Circuit Type:
AC 50/60 Hz
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Power Dissipation Per Pole:
0.36 W AC-3 || 1.56 W AC-1 || 0.36 W AC-3e
Pollution Degree:
3
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Height:
77 mm
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
[Uc] Control Circuit Voltage:
220 V AC 50/60 Hz
Sustainable Offer Status:
Green Premium product
$142.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200 to 208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. Contactor is supplied with a 480 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.