Schneider Electric

Schneider Electric LC1D1286U7 IEC contactor, TeSys Deca, nonreversing, 25A resistive, 4 pole, 2 NO and 2 NC, 240VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D1286U7
MPN:
LC1D1286U7
Condition:
New
Ip Degree Of Protection:
IP20 front face IEC 60529
Height:
85 mm
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals flat Ø 8 mm M3.5 || power circuit 1.7 N.m lugs-ring terminals Philips No 2 M3
Width:
45 mm
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Product Certifications:
UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Rohs Exemption Information:
Yes
Range Of Product:
TeSys Deca
Minimum Switching Voltage:
17 V for Signaling circuit
Warranty:
18 months
Coil Technology:
without built-in suppressor module
Power Dissipation Per Pole:
1.56 W AC-1
Protective Treatment:
THIEC 60068-2-30
Country of Origin:
Czechia
Circularity Profile:
ENVEOLI1501004
Eu Rohs Directive:
Compliant
Electrical Durability:
0.8 Mcycles 25 A AC-1 <= 440 V
Auxiliary Contact Composition:
1 NO + 1 NC
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Toxic Heavy Metal Free:
Yes
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Pvc Free:
Yes
Signaling Circuit Frequency:
25...400 Hz
Maximum Operating Rate:
3600 cyc/h 60°C
Environmental Disclosure:
ENVPEP1501004
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Mechanical Durability:
15 Mcycles
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Compatibility Code:
LC1D
Mounting Support:
rail || plate
[Uc] Control Circuit Voltage:
240 V AC 50/60 Hz
Standards:
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Flame Retardance:
V1 conforming to UL 94
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 8 mm
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-60°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Operating Altitude:
0...9842.52 ft (0...3000 m)
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Heat Dissipation:
2-3 W at 50/60 Hz
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Operating Time:
12...22 ms closing || 4...19 ms opening
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
$165.60

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 25A resistive load rating. Contactor is supplied with a 240 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose