Schneider Electric

Schneider Electric LC1D128E7 IEC contactor, TeSys Deca, nonreversing, 25A resistive, 4 pole, 2 NO and 2 NC, 48VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D128E7
MPN:
LC1D128E7
Condition:
New
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Rohs Exemption Information:
Yes
Width:
45 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Control Circuit Type:
AC 50/60 Hz
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Warranty:
18 months
Protective Cover:
with
Net Weight:
0.365 kg
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Signaling Circuit Frequency:
25...400 Hz
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Auxiliary Contact Composition:
1 NO + 1 NC
Maximum Operating Rate:
3600 cyc/h 60°C
Eu Rohs Directive:
Compliant
Product Or Component Type:
contactor
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Power Dissipation Per Pole:
1.56 W AC-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Ip Degree Of Protection:
IP20 front face IEC 60529
[Uc] Control Circuit Voltage:
48 V AC 50/60 Hz
Range Of Product:
TeSys Deca
Compatibility Code:
LC1D
Coil Technology:
without built-in suppressor module
Pvc Free:
Yes
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Depth:
92 mm
Minimum Switching Voltage:
17 V for Signaling circuit
Contactor Application:
resistive load
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Mechanical Durability:
15 Mcycles
Country of Origin:
France
Insulation Resistance:
> 10 MOhm for Signaling circuit
Fire Resistance:
850°C IEC 60695-2-1
Overvoltage Category:
III
Weight:
0.365 kg
Environmental Disclosure:
ENVPEP1501004
Mounting Support:
rail || plate
Pollution Degree:
3
Poles Description:
4P
Flame Retardance:
V1 conforming to UL 94
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Sustainable Offer Status:
Green Premium product
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
$165.60

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 25A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose