Schneider Electric LC1D128ED IEC contactor, TeSys Deca, nonreversing, 25A resistive, 4 pole, 2 NO and 2 NC, 48VDC coil, open style
Schneider Electric
$172.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 25A resistive load rating. Contactor is supplied with a 48 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 1.16 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Depth:
- 99 mm
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
- Time Constant:
- 28 ms
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Product Certifications:
- GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
- Protective Cover:
- with
- Pollution Degree:
- 3
- Inrush Power In W:
- 5.4-5.4 W 20°C)
- Overvoltage Category:
- III
- Compatibility Code:
- LC1D
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Width:
- 45 mm
- Country of Origin:
- France
- Pvc Free:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Signaling Circuit Frequency:
- 25...400 Hz
- Operating Time:
- 63±15 % ms closing || 20±20 % ms opening
- Power Dissipation Per Pole:
- 1.56 W AC-1
- Weight:
- 0.525 kg
- Mechanical Durability:
- 30 Mcycles
- Mounting Support:
- plate || rail
- Range Of Product:
- TeSys Deca
- Device Short Name:
- LC1D
- Control Circuit Voltage Limits:
- 0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Environmental Disclosure:
- ENVPEP110230EN
- [Uc] Control Circuit Voltage:
- 48 V DC
- Mercury Free:
- Yes
- Warranty:
- 18 months
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Net Weight:
- 0.525 kg
- Control Circuit Type:
- DC standard
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Protective Treatment:
- THIEC 60068-2-30
- Pole Contact Composition:
- 2 NO + 2 NC
- Poles Description:
- 4P
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Rohs Exemption Information:
- Yes
- Coil Technology:
- with integral suppression device
- Flame Retardance:
- V1 conforming to UL 94
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Contactor Application:
- resistive load
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Average Impedance:
- 2.5 mOhm - Ith 25 A 50 Hz for power circuit
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947