Schneider Electric LC1D128F7 IEC contactor, TeSys Deca, nonreversing, 25A resistive, 4 pole, 2 NO and 2 NC, 110VAC 50/60Hz coil, open style
Schneider Electric
$165.60
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 25A resistive load rating. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Fire Resistance:
- 850°C IEC 60695-2-1
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- [Icw] Rated Short-Time Withstand Current:
- 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Power Dissipation Per Pole:
- 1.56 W AC-1
- Rohs Exemption Information:
- Yes
- Contactor Application:
- resistive load
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Pvc Free:
- Yes
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Toxic Heavy Metal Free:
- Yes
- Poles Description:
- 4P
- Weight:
- 0.365 kg
- Range Of Product:
- TeSys Deca
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
- Product Certifications:
- GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
- Protective Cover:
- with
- Eu Rohs Directive:
- Compliant
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Electrical Durability:
- 0.8 Mcycles 25 A AC-1 <= 440 V
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Environmental Disclosure:
- ENVPEP1501004
- Product Or Component Type:
- contactor
- Pollution Degree:
- 3
- Control Circuit Type:
- AC 50/60 Hz
- Flame Retardance:
- V1 conforming to UL 94
- Overvoltage Category:
- III
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Net Weight:
- 0.365 kg
- Compatibility Code:
- LC1D
- Pole Contact Composition:
- 2 NO + 2 NC
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Device Short Name:
- LC1D
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Warranty:
- 18 months
- Associated Fuse Rating: