Schneider Electric

Schneider Electric LC1D128FD IEC contactor, TeSys Deca, nonreversing, 25A resistive, 4 pole, 2 NO and 2 NC, 110VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D128FD
MPN:
LC1D128FD
Condition:
New
Poles Description:
4P
[Uc] Control Circuit Voltage:
110 V DC
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Power Dissipation Per Pole:
1.56 W AC-1
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
Minimum Switching Current:
5 mA for Signaling circuit
Overvoltage Category:
III
Height:
85 mm
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Coil Technology:
with integral suppression device
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Rohs Exemption Information:
Yes
Connections - Terminals:
power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable
Ip Degree Of Protection:
IP20 front face IEC 60529
Compatibility Code:
LC1D
Control Circuit Type:
DC standard
Minimum Switching Voltage:
17 V for Signaling circuit
Protective Cover:
with
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Net Weight:
0.525 kg
Eu Rohs Directive:
Compliant with Exemptions
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Pole Contact Composition:
2 NO + 2 NC
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Depth:
99 mm
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Weight:
0.525 kg
Mechanical Durability:
30 Mcycles
Protective Treatment:
THIEC 60068-2-30
Pvc Free:
Yes
Auxiliary Contact Composition:
1 NO + 1 NC
Maximum Operating Rate:
3600 cyc/h 60°C
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Flame Retardance:
V1 conforming to UL 94
Fire Resistance:
850°C IEC 60695-2-1
Product Or Component Type:
contactor
Operating Altitude:
0...9842.52 ft (0...3000 m)
Device Short Name:
LC1D
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Range Of Product:
TeSys Deca
Operating Time:
63±15 % ms closing || 20±20 % ms opening
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Warranty:
18 months
Insulation Resistance:
> 10 MOhm for Signaling circuit
$172.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 25A resistive load rating. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 1.16 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose