Schneider Electric LC1D12BNE IEC contactor, TeSys Deca Green, nonreversing, 12A, 7.5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24/60VAC/VDC coil
Schneider Electric
$47.00
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 30A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 24-60V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Compatibility Code:
- LC1D
- Coil Technology:
- built-in bidirectional peak limiting
- Protective Cover:
- with
- Pollution Degree:
- 3
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Hold-In Power Consumption In W:
- 0.6-0.6 W 20°C
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
- Overvoltage Category:
- III
- Product Or Component Type:
- contactor
- Range:
- TeSys || TeSys Deca
- Utilisation Category:
- AC-3 || AC-1 || AC-3e
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Halogen Content Performance:
- Halogen free plastic parts & cables product
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Net Weight:
- 0.373 kg
- Mounting Support:
- rail || plate
- Flame Retardance:
- V1 conforming to UL 94
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC-1 for power circuit || 12 A (at <60°C) at <= 440 V AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC-3e for power circuit
- Inrush Power In Va:
- 15-15 VA 50/60 Hz (at 20°C)
- Hold-In Power Consumption In Va:
- 0.9-0.9 VA 50/60 Hz (at 20°C)
- Range Of Product:
- TeSys Deca
- Depth:
- 86 mm
- Circularity Profile:
- ENVEOLI1609001EN
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Warranty:
- 18 months
- Sustainable Offer Status:
- Green Premium product
- Product Certifications:
- CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
- Device Short Name:
- LC1D
- Heat Dissipation:
- 0.6-0.6 W at 50/60 Hz
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || power
- Operating Time:
- 45...55 ms closing || 20...90 ms opening
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Electrical Durability:
- 2.3 Mcycles 11 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2.3 Mcycles 11 A AC-3e <= 440 V
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Minimum Switching Current:
- 5 mA for Signaling circuit
- [Uc] Control Circuit Voltage:
- 24...60 V AC 50/60 Hz || 24...60 V DC
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Eu Rohs Directive:
- Compliant with Exemptions
- Mercury Free:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Connections - Terminals:
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
- Power Dissipation Per Pole:
- 1.56 W AC-1 || 0.36 W AC-3 || 0.36 W AC-3e
- Contactor Application:
- resistive load || motor control
- Signaling Circuit Frequency:
- 25...400 Hz
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- Minimum Switching Voltage:
- 17 V for Signaling circuit