Schneider Electric

Schneider Electric LC1D12LE7 IEC contactor, TeSys Deca, nonreversing, 12A, 7.5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 208VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D12LE7
MPN:
LC1D12LE7
Condition:
New
Operating Altitude:
0...9842.52 ft (0...3000 m)
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Operating Time:
12...22 ms closing || 4...19 ms opening
Depth:
86 mm
Maximum Operating Rate:
3600 cyc/h 60°C
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Warranty:
18 months
Electrical Durability:
2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 12 A AC-3e <= 440 V
Environmental Disclosure:
ENVPEP1501004
Mechanical Durability:
15 Mcycles
Utilisation Category:
AC-1 || AC-3 || AC-4 || AC-3e
Device Short Name:
LC1D
Height:
77 mm
Contactor Application:
resistive load || motor control
Net Weight:
0.325 kg
Fire Resistance:
850°C IEC 60695-2-1
Minimum Switching Voltage:
17 V for Signaling circuit
Control Circuit Type:
AC 50/60 Hz
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Insulation Resistance:
> 10 MOhm for Signaling circuit
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Ip Degree Of Protection:
IP20 front face IEC 60529
Minimum Switching Current:
5 mA for Signaling circuit
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Signaling Circuit Frequency:
25...400 Hz
Poles Description:
3P
Range Of Product:
TeSys Deca
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Heat Dissipation:
2-3 W at 50/60 Hz
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Coil Technology:
without built-in suppressor module
Compatibility Code:
LC1D
Flame Retardance:
V1 conforming to UL 94
Weight:
0.325 kg
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Uc] Control Circuit Voltage:
208 V AC 50/60 Hz
Power Dissipation Per Pole:
0.36 W AC-3 || 1.56 W AC-1 || 0.36 W AC-3e
Overvoltage Category:
III
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Maximum Horse Power Rating:
0.5 hp at 115 V AC 50/60 Hz for 1 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 3 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 3 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 460/480 V AC 50/60 Hz for 3 phase
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Eu Rohs Directive:
Compliant
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
$142.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 30A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 208 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose