Schneider Electric

Schneider Electric LC1D12P7 IEC contactor, TeSys Deca, nonreversing, 12A, 7.5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 230VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D12P7
MPN:
LC1D12P7
Condition:
New
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
Protective Cover:
with
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Signaling Circuit Frequency:
25...400 Hz
Minimum Switching Voltage:
17 V for Signaling circuit
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Environmental Disclosure:
ENVPEP1501004
Net Weight:
0.325 kg
Product Or Component Type:
contactor
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Country of Origin:
Indonesia
Pollution Degree:
3
Pole Contact Composition:
3 NO
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Eu Rohs Directive:
Compliant
Insulation Resistance:
> 10 MOhm for Signaling circuit
Coil Technology:
without built-in suppressor module
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Operating Time:
12...22 ms closing || 4...19 ms opening
Electrical Durability:
2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 12 A AC-3e <= 440 V
Overvoltage Category:
III
Heat Dissipation:
2-3 W at 50/60 Hz
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Depth:
86 mm
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Toxic Heavy Metal Free:
Yes
Circularity Profile:
ENVEOLI1501004
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Compatibility Code:
LC1D
Poles Description:
3P
Minimum Switching Current:
5 mA for Signaling circuit
Sustainable Offer Status:
Green Premium product
Ip Degree Of Protection:
IP20 front face IEC 60529
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Rohs Exemption Information:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Device Short Name:
LC1D
Auxiliary Contact Composition:
1 NO + 1 NC
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
[Uc] Control Circuit Voltage:
230 V AC 50/60 Hz
$142.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 30A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose