Schneider Electric

Schneider Electric LC1D12Z7 IEC contactor, TeSys Deca, nonreversing, 12A, 7.5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 21VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D12Z7
MPN:
LC1D12Z7
Condition:
New
Pvc Free:
Yes
Insulation Resistance:
> 10 MOhm for Signaling circuit
Net Weight:
0.325 kg
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Motor Power Kw:
3 kW at 220...230 V AC 50/60 Hz (AC-3) || 5.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 5.5 kW at 415...440 V AC 50/60 Hz (AC-3) || 7.5 kW at 500 V AC 50/60 Hz (AC-3) || 7.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 3.7 kW at 400 V AC 50/60 Hz (AC-4) ||
Device Short Name:
LC1D
Electrical Durability:
2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 12 A AC-3e <= 440 V
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Toxic Heavy Metal Free:
Yes
Range Of Product:
TeSys Deca
Poles Description:
3P
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Connections - Terminals:
power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable
[Uc] Control Circuit Voltage:
21 V AC 50/60 Hz
Power Dissipation Per Pole:
0.36 W AC-3 || 1.56 W AC-1 || 0.36 W AC-3e
Depth:
86 mm
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Country of Origin:
France
Protective Cover:
with
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Pollution Degree:
3
Mechanical Durability:
15 Mcycles
Ip Degree Of Protection:
IP20 front face IEC 60529
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Pole Contact Composition:
3 NO
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Eu Rohs Directive:
Compliant
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
Minimum Switching Current:
5 mA for Signaling circuit
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Warranty:
18 months
Signaling Circuit Frequency:
25...400 Hz
Compatibility Code:
LC1D
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Operating Altitude:
0...9842.52 ft (0...3000 m)
Auxiliary Contact Composition:
1 NO + 1 NC
Height:
77 mm
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Environmental Disclosure:
ENVPEP1501004
Protective Treatment:
THIEC 60068-2-30
Mercury Free:
Yes
Control Circuit Type:
AC 50/60 Hz
Product Or Component Type:
contactor
Operating Time:
12...22 ms closing || 4...19 ms opening
$164.22

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 30A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 21 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose