Schneider Electric

Schneider Electric LC1D1506BD IEC contactor, TeSys Deca, nonreversing, 150A, 100HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D1506BD
MPN:
LC1D1506BD
Condition:
New
Hold-In Power Consumption In W:
2.4-5.1 W 20°C
Safety Reliability Level:
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Pollution Degree:
3
Circularity Profile:
ENVEOLI100405EN
Net Weight:
2.5 kg
Contactor Application:
motor control || resistive load
Fire Resistance:
850°C IEC 60695-2-1
Warranty:
18 months
Minimum Switching Current:
5 mA for Signaling circuit
Rohs Exemption Information:
Yes
Compatibility Code:
LC1D
Width:
120 mm
Product Certifications:
UL || CCC || CSA || CE || UKCA || Marine || EAC
Mechanical Durability:
8 Mcycles
Signaling Circuit Frequency:
25...400 Hz
Electrical Durability:
0.85 Mcycles 150 A AC-3 <= 440 V || 1 Mcycles 200 A AC-1 <= 440 V || 0.85 Mcycles 150 A AC-3e <= 440 V
Climatic Withstand:
IACS E10 exposure to damp heat
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Device Short Name:
LC1D
Depth:
136 mm
Environmental Disclosure:
ENVPEP060301EN
Protective Cover:
with
Product Or Component Type:
contactor
Inrush Power In W:
270-365 W 20°C)
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
Control Circuit Voltage Limits:
0.75...1.2 Uc -40-55°C operational DC || 0.15...0.4 Uc -40-70°C drop-out DC || 1...1.2 Uc 55-70°C operational DC
Control Circuit Type:
DC standard
Tightening Torque:
control circuit 1.2 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.2 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 12 N.m lugs-ring terminals hexagonal 13 mm M8 || power circuit 12 N.m bars hexagonal 13 mm M8 || control c
Sustainable Offer Status:
Green Premium product
Auxiliary Contact Composition:
1 NO + 1 NC
Country of Origin:
France
Rated Breaking Capacity:
1400 A at 440 V for power circuit conforming to IEC 60947
Insulation Resistance:
> 10 MOhm for Signaling circuit
Minimum Switching Voltage:
17 V for Signaling circuit
Maximum Horse Power Rating:
40 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 50 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 100 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 125 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Motor Power Kw:
40 kW at 220...230 V AC 50/60 Hz (AC-3) || 75 kW at 380...400 V AC 50/60 Hz (AC-3) || 80 kW at 415...440 V AC 50/60 Hz (AC-3) || 90 kW at 500 V AC 50/60 Hz (AC-3) || 100 kW at 660...690 V AC 50/60 Hz (AC-3) || 75 kW at 1000 V AC 50/60 Hz (AC-3) || 22
Pole Contact Composition:
3 NO
[Ue] Rated Operational Voltage:
power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 315 A gG at <= 690 V coordination type 1 for power circuit || 250 A gG at <= 690 V coordination type 2 for power circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
Protective Treatment:
THIEC 60068-2-30
Time Constant:
25 ms
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Coil Technology:
with integral suppression device
[Icw] Rated Short-Time Withstand Current:
250 A 40°C - 10 min for power circuit || 580 A 40°C - 1 min for power circuit || 1200 A 40°C - 10 s for power circuit || 1400 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 m
Operating Time:
20...35 ms closing || 40...75 ms opening
Weight:
2.5 kg
Pvc Free:
Yes
$696.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 150A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 40HP at 200 to 208VAC, 50HP at 240VAC, 100HP at 480VAC and 125HP at 600VAC three phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose