Schneider Electric LC1D1506LE7 IEC contactor, TeSys Deca, nonreversing, 150A, 100HP at 480VAC, 3 phase, 3 pole, 3 NO, 208VAC 50/60Hz coil, open style
Schneider Electric
$800.40
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 150A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 40HP at 200 to 208VAC, 50HP at 240VAC, 100HP at 480VAC and 125HP at 600VAC three phase. Contactor is supplied with a 208 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Range Of Product:
- TeSys Deca
- Mounting Support:
- rail || plate
- Rohs Exemption Information:
- Yes
- Depth:
- 136 mm
- Hold-In Power Consumption In Va:
- 2-18 VA 60 Hz cos phi 0.9 (at 20°C) || 2-18 VA 50 Hz cos phi 0.9 (at 20°C)
- Device Short Name:
- LC1D
- Poles Description:
- 3P
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 315 A gG at <= 690 V coordination type 1 for power circuit || 250 A gG at <= 690 V coordination type 2 for power circuit
- [Ue] Rated Operational Voltage:
- power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
- [Ie] Rated Operational Current:
- 200 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 150 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 150 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Motor Power Kw:
- 40 kW at 220...230 V AC 50/60 Hz (AC-3) || 75 kW at 380...400 V AC 50/60 Hz (AC-3) || 80 kW at 415...440 V AC 50/60 Hz (AC-3) || 90 kW at 500 V AC 50/60 Hz (AC-3) || 100 kW at 660...690 V AC 50/60 Hz (AC-3) || 75 kW at 1000 V AC 50/60 Hz (AC-3) || 22
- Protective Cover:
- with
- Protective Treatment:
- THIEC 60068-2-30
- Tightening Torque:
- control circuit 1.2 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.2 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 12 N.m lugs-ring terminals hexagonal 13 mm M8 || power circuit 12 N.m bars hexagonal 13 mm M8 || control c
- Sustainable Offer Status:
- Green Premium product
- Weight:
- 2.5 kg
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || IEC 60947-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
- Electrical Durability:
- 0.85 Mcycles 150 A AC-3 <= 440 V || 1 Mcycles 200 A AC-1 <= 440 V || 0.85 Mcycles 150 A AC-3e <= 440 V
- [Uc] Control Circuit Voltage:
- 208 V AC 50/60 Hz
- Pollution Degree:
- 3
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1660 A at 440 V for power circuit conforming to IEC 60947
- Flame Retardance:
- V1 conforming to UL 94
- Inrush Power In Va:
- 280-350 VA 60 Hz cos phi 0.9 (at 20°C) || 280-350 VA 50 Hz cos phi 0.9 (at 20°C)
- Fire Resistance:
- 850°C IEC 60695-2-1
- Eu Rohs Directive:
- Compliant with Exemptions
- Pvc Free:
- Yes
- Circularity Profile:
- ENVEOLI100405EN
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Signaling Circuit Frequency:
- 25...400 Hz
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947
- Maximum Operating Rate:
- 1200 cyc/h 60°C
- Power Dissipation Per Pole:
- 24 W AC-1 || 13.5 W AC-3 || 13.5 W AC-3e
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Control Circuit Type:
- AC 50/60 Hz
- Warranty:
- 18 months
- Maximum Horse Power Rating:
- 40 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 50 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 100 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 125 hp at 575/600 V AC 50/60 Hz for 3 phase motors
- Operating Time:
- 20...35 ms closing || 40...75 ms opening
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Rated Breaking Capacity:
- 1400 A at 440 V for power circuit conforming to IEC 60947
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Weee: