Schneider Electric

Schneider Electric LC1D183B7 IEC contactor, TeSys Deca, nonreversing, 18A, 10HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D183B7
MPN:
LC1D183B7
Condition:
New
Auxiliary Contact Composition:
1 NO + 1 NC
Weight:
0.33 kg
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Protective Treatment:
THIEC 60068-2-30
Warranty:
18 months
Fire Resistance:
850°C IEC 60695-2-1
Minimum Switching Voltage:
17 V for Signaling circuit
Power Dissipation Per Pole:
2.5 W AC-1 || 0.8 W AC-3 || 0.8 W AC-3e
Circularity Profile:
ENVEOLI1501004
Maximum Operating Rate:
3600 cyc/h 60°C
Operating Altitude:
0...9842.52 ft (0...3000 m)
Mounting Support:
plate || rail
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Maximum Horse Power Rating:
1 hp at 115 V AC 50/60 Hz for 1 phase motors || 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 5 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 460/480 V AC 50/60 Hz for 3 phase mot
Sustainable Offer Status:
Green Premium product
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Control Circuit Type:
AC 50/60 Hz
Range Of Product:
TeSys Deca
Rohs Exemption Information:
Yes
Rated Breaking Capacity:
300 A at 440 V for power circuit conforming to IEC 60947
Protective Cover:
with
Signaling Circuit Frequency:
25...400 Hz
Contactor Application:
motor control || resistive load
Heat Dissipation:
2-3 W at 50/60 Hz
Ip Degree Of Protection:
IP20 front face IEC 60529
Toxic Heavy Metal Free:
Yes
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Overvoltage Category:
III
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Insulation Resistance:
> 10 MOhm for Signaling circuit
[Ie] Rated Operational Current:
18 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 18 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Product Or Component Type:
contactor
Product Certifications:
UL || BV || LROS (Lloyds register of shipping) || RINA || CSA || CCC || GOST || DNV || GL || UKCA
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Flame Retardance:
V1 conforming to UL 94
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Country of Origin:
United States
Eu Rohs Directive:
Compliant
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Device Short Name:
LC1D
[Icw] Rated Short-Time Withstand Current:
145 A 40°C - 10 s for power circuit || 240 A 40°C - 1 s for power circuit || 40 A 40°C - 10 min for power circuit || 84 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
$163.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200 to 208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.90 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose