Schneider Electric

Schneider Electric LC1D183G7 IEC contactor, TeSys Deca, nonreversing, 18A, 10HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D183G7
MPN:
LC1D183G7
Condition:
New
Pole Contact Composition:
3 NO
Pollution Degree:
3
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Signaling Circuit Frequency:
25...400 Hz
Maximum Horse Power Rating:
1 hp at 115 V AC 50/60 Hz for 1 phase motors || 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 5 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 460/480 V AC 50/60 Hz for 3 phase mot
Mounting Support:
plate || rail
Motor Power Kw:
4 kW at 220...230 V AC 50/60 Hz (AC-3) || 7.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 9 kW at 415...440 V AC 50/60 Hz (AC-3) || 10 kW at 500 V AC 50/60 Hz (AC-3) || 10 kW at 660...690 V AC 50/60 Hz (AC-3) || 4 kW at 400 V AC 50/60 Hz (AC-4) || 4 kW a
Minimum Switching Voltage:
17 V for Signaling circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs Directive:
Compliant
Rohs Exemption Information:
Yes
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Product Certifications:
BV || RINA || CSA || CCC || GL || UL || DNV || GOST || LROS (Lloyds register of shipping) || UKCA
[Ie] Rated Operational Current:
18 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 18 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Maximum Operating Rate:
3600 cyc/h 60°C
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Protective Treatment:
THIEC 60068-2-30
Compatibility Code:
LC1D
Overvoltage Category:
III
Poles Description:
3P
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Net Weight:
0.33 kg
Power Dissipation Per Pole:
2.5 W AC-1 || 0.8 W AC-3 || 0.8 W AC-3e
Environmental Disclosure:
ENVPEP1501004
Depth:
86 mm
Circularity Profile:
ENVEOLI1501004
Minimum Switching Current:
5 mA for Signaling circuit
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
[Icw] Rated Short-Time Withstand Current:
145 A 40°C - 10 s for power circuit || 240 A 40°C - 1 s for power circuit || 40 A 40°C - 10 min for power circuit || 84 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
[Uc] Control Circuit Voltage:
120 V AC 50/60 Hz
Warranty:
18 months
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Mercury Free:
Yes
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Heat Dissipation:
2-3 W at 50/60 Hz
Ip Degree Of Protection:
IP20 front face IEC 60529
Sustainable Offer Status:
Green Premium product
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Or Component Type:
contactor
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
$187.68

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200 to 208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.90 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose