Schneider Electric

Schneider Electric LC1D183M7 IEC contactor, TeSys Deca, nonreversing, 18A, 10HP at 480VAC, 3 phase, 3 pole, 3 NO, 220VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D183M7
MPN:
LC1D183M7
Condition:
New
[Icw] Rated Short-Time Withstand Current:
145 A 40°C - 10 s for power circuit || 240 A 40°C - 1 s for power circuit || 40 A 40°C - 10 min for power circuit || 84 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Height:
99 mm
Flame Retardance:
V1 conforming to UL 94
Protective Treatment:
THIEC 60068-2-30
Rohs Exemption Information:
Yes
Minimum Switching Voltage:
17 V for Signaling circuit
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability:
15 Mcycles
Auxiliary Contact Composition:
1 NO + 1 NC
Coil Technology:
without built-in suppressor module
Pvc Free:
Yes
Control Circuit Type:
AC 50/60 Hz
Contactor Application:
motor control || resistive load
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Rated Breaking Capacity:
300 A at 440 V for power circuit conforming to IEC 60947
Sustainable Offer Status:
Green Premium product
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Fire Resistance:
850°C IEC 60695-2-1
Motor Power Kw:
4 kW at 220...230 V AC 50/60 Hz (AC-3) || 7.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 9 kW at 415...440 V AC 50/60 Hz (AC-3) || 10 kW at 500 V AC 50/60 Hz (AC-3) || 10 kW at 660...690 V AC 50/60 Hz (AC-3) || 4 kW at 400 V AC 50/60 Hz (AC-4) || 4 kW a
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Ip Degree Of Protection:
IP20 front face IEC 60529
Country of Origin:
Indonesia
Weight:
0.33 kg
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
Depth:
86 mm
Circularity Profile:
ENVEOLI1501004
Maximum Operating Rate:
3600 cyc/h 60°C
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Ie] Rated Operational Current:
18 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 18 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Eu Rohs Directive:
Compliant
Protective Cover:
with
Range Of Product:
TeSys Deca
Product Or Component Type:
contactor
Operating Altitude:
0...9842.52 ft (0...3000 m)
Minimum Switching Current:
5 mA for Signaling circuit
Maximum Horse Power Rating:
1 hp at 115 V AC 50/60 Hz for 1 phase motors || 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 5 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 460/480 V AC 50/60 Hz for 3 phase mot
Heat Dissipation:
2-3 W at 50/60 Hz
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Power Dissipation Per Pole:
2.5 W AC-1 || 0.8 W AC-3 || 0.8 W AC-3e
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Electrical Durability:
1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
Pollution Degree:
3
$163.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200 to 208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.90 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose