Schneider Electric

Schneider Electric LC1D18EHE IEC contactor, TeSys Deca Green, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 48/130VAC/VDC coil

(No reviews yet) Write a Review
SKU:
LC1D18EHE
MPN:
LC1D18EHE
Condition:
New
Power Dissipation Per Pole:
2.5 W AC-1 || 0.8 W AC-3 || 0.8 W AC-3e
Insulation Resistance:
> 10 MOhm for Signaling circuit
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz
Average Impedance:
2.5 mOhm - Ith 32 A 50 Hz for power circuit
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Inrush Power In Va:
25-25 VA 50/60 Hz (at 20°C)
Auxiliary Contact Composition:
1 NO + 1 NC
Protective Cover:
with
Weight:
0.378 kg
[Ie] Rated Operational Current:
18 A (at <60°C) at <= 440 V AC-3 for power circuit || 32 A (at <60°C) at <= 440 V AC-1 for power circuit || 18 A (at <60°C) at <= 440 V AC-3e for power circuit
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
Eu Rohs Directive:
Compliant with Exemptions
Motor Power Kw:
4 kW at 220...230 V AC 50 Hz (AC-3) || 7.5 kW at 380...400 V AC 50 Hz (AC-3) || 9 kW at 415 V AC 50 Hz (AC-3) || 9 kW at 440 V AC 50 Hz (AC-3) || 10 kW at 500 V AC 50 Hz (AC-3) || 10 kW at 660...690 V AC 50 Hz (AC-3) || 4 kW at 220...230 V AC 50 Hz (
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Pollution Degree:
3
Inrush Power In W:
24-24 W 20°C)
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Fire Resistance:
850°C IEC 60695-2-1
Mounting Support:
rail || plate
Product Certifications:
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Environmental Disclosure:
ENVPEP1609001EN
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Signaling Circuit Frequency:
25...400 Hz
Contactor Application:
resistive load || motor control
Minimum Switching Voltage:
17 V for Signaling circuit
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Rohs Exemption Information:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Range Of Product:
TeSys Deca
Product Or Component Type:
contactor
Hold-In Power Consumption In W:
0.8-0.8 W 20°C
Halogen Content Performance:
Halogen free plastic parts & cables product
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || power
Heat Dissipation:
0.8-0.8 W at 50/60 Hz
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
Coil Technology:
built-in bidirectional peak limiting
Control Circuit Voltage Limits:
<= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC/DC || 1...1.1 Uc 60-70°C operational AC/DC
Warranty:
18 months
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms for Signaling circuit || 40 A 40°C - 10 min for power circuit || 84 A 40°C - 1 min for power circuit || 145 A 40°C - 10 s for power circuit || 240 A 40°C - 1
Overvoltage Category:
III
Flame Retardance:
V1 conforming to UL 94
Operating Time:
45...55 ms closing || 20...90 ms opening
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 32 A (at 60°C) for power circuit
Compatibility Code:
LC1D
Range:
TeSys || TeSys Deca
Mechanical Durability:
15 Mcycles
$57.00

Description

TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 48-130V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.83 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.