Schneider Electric

Schneider Electric LC1D18FC7 IEC contactor, TeSys Deca, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 127VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D18FC7
MPN:
LC1D18FC7
Condition:
New
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Product Certifications:
DNV || GOST || CSA || CCC || LROS (Lloyds register of shipping) || GL || UL || BV || RINA || UKCA
Eu Rohs Directive:
Compliant
Poles Description:
3P
Protective Treatment:
THIEC 60068-2-30
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Pole Contact Composition:
3 NO
Power Dissipation Per Pole:
2.5 W AC-1 || 0.8 W AC-3
Minimum Switching Current:
5 mA for Signaling circuit
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Compatibility Code:
LC1D
Maximum Operating Rate:
3600 cyc/h 60°C
Pollution Degree:
3
Net Weight:
0.33 kg
Range Of Product:
TeSys Deca
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Toxic Heavy Metal Free:
Yes
Mounting Support:
rail || plate
Maximum Horse Power Rating:
1 hp at 115 V AC 50/60 Hz for 1 phase motors || 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 5 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 460/480 V AC 50/60 Hz for 3 phase mot
Average Impedance:
2.5 mOhm - Ith 32 A 50 Hz for power circuit
Operating Time:
12...22 ms closing || 4...19 ms opening
Depth:
86 mm
Signaling Circuit Frequency:
25...400 Hz
Rated Breaking Capacity:
300 A at 440 V for power circuit conforming to IEC 60947
Environmental Disclosure:
ENVPEP1501004
Operating Altitude:
0...9842.52 ft (0...3000 m)
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Auxiliary Contact Composition:
1 NO + 1 NC
Overvoltage Category:
III
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
[Icw] Rated Short-Time Withstand Current:
145 A 40°C - 10 s for power circuit || 240 A 40°C - 1 s for power circuit || 40 A 40°C - 10 min for power circuit || 84 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Mercury Free:
Yes
Heat Dissipation:
2-3 W at 50/60 Hz
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Mechanical Durability:
15 Mcycles
Insulation Resistance:
> 10 MOhm for Signaling circuit
Fire Resistance:
850°C IEC 60695-2-1
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Country of Origin:
France
Sustainable Offer Status:
Green Premium product
Rohs Exemption Information:
Yes
$163.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 127 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose