[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 10 mm
Operating Altitude:
0...9842.52 ft (0...3000 m)
Insulation Resistance:
> 10 MOhm for Signaling circuit
Overvoltage Category:
III
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Device Short Name:
LC1D
Pollution Degree:
3
Fire Resistance:
850°C IEC 60695-2-1
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Circularity Profile:
ENVEOLI1102030EN
Country of Origin:
Singapore
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
Contactor Application:
motor control || resistive load
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Net Weight:
0.53 kg
Auxiliary Contact Composition:
1 NO + 1 NC
Signaling Circuit Frequency:
25...400 Hz
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
Maximum Operating Rate:
3600 cyc/h 60°C
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
[Uc] Control Circuit Voltage:
24 V DC
Height:
85 mm
Weight:
0.53 kg
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Minimum Switching Current:
5 mA for Signaling circuit
Product Or Component Type:
contactor
Motor Power Kw:
5.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 11 kW at 380...400 V AC 50/60 Hz (AC-3) || 11 kW at 415...440 V AC 50/60 Hz (AC-3) || 15 kW at 500 V AC 50/60 Hz (AC-3) || 15 kW at 660...690 V AC 50/60 Hz (AC-3) || 5.5 kW at 400 V AC 50/60 Hz (AC-4) || 5.
Electrical Durability:
1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
Width:
45 mm
Power Dissipation Per Pole:
3.2 W AC-1 || 1.25 W AC-3 || 1.25 W AC-3e
[Icw] Rated Short-Time Withstand Current:
240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Rated Breaking Capacity:
450 A at 440 V for power circuit conforming to IEC 60947
Range Of Product:
TeSys Deca
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Ip Degree Of Protection:
IP20 front face IEC 60529
Environmental Disclosure:
ENVPEP110230EN
Operating Time:
63±15 % ms closing || 20±20 % ms opening
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4 |
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Flame Retardance:
V1 conforming to UL 94
Inrush Power In W:
5.4-5.4 W 20°C)
Mounting Support:
rail || plate
$189.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.17 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.