Schneider Electric

Schneider Electric LC1D256SD IEC contactor, TeSys D, nonreversing, 25A, 15HP at 480VAC, 3 phase, 3 pole, 3 NO, 72VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D256SD
MPN:
LC1D256SD
Condition:
New
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Net Weight:
0.53 kg
Inrush Power In W:
5.4-5.4 W 20°C)
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Signaling Circuit Frequency:
25...400 Hz
Sustainable Offer Status:
Green Premium product
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Device Short Name:
LC1D
Pollution Degree:
3
Minimum Switching Current:
5 mA for Signaling circuit
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Insulation Resistance:
> 10 MOhm for Signaling circuit
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Product Or Component Type:
contactor
Maximum Operating Rate:
3600 cyc/h 60°C
Operating Altitude:
0...9842.52 ft (0...3000 m)
Minimum Switching Voltage:
17 V for Signaling circuit
Depth:
101 mm
Electrical Durability:
1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
Height:
85 mm
Ip Degree Of Protection:
IP20 front face IEC 60529
Width:
45 mm
Contactor Application:
resistive load || motor control
Mercury Free:
Yes
Warranty:
18 months
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Country of Origin:
France
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4
Utilisation Category:
AC-1 || AC-4 || AC-3 || AC-3e
Protective Cover:
with
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Product Certifications:
LROS (Lloyds register of shipping) || CCC || BV || RINA || CSA || GOST || UL || DNV || GL || UKCA
Flame Retardance:
V1 conforming to UL 94
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Power Dissipation Per Pole:
3.2 W AC-1 || 1.25 W AC-3 || 1.25 W AC-3e
Time Constant:
28 ms
[Uc] Control Circuit Voltage:
72 V DC
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Operating Time:
63±15 % ms closing || 20±20 % ms opening
Circularity Profile:
ENVEOLI1102030EN
Overvoltage Category:
III
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 10 mm
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Range Of Product:
TeSys Deca
Mounting Support:
plate || rail
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
$189.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.17 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose