Schneider Electric

Schneider Electric LC1D2583E7 IEC contactor, TeSys D, nonreversing, 40A resistive, 4 pole, 2 NO and 2 NC, 48VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D2583E7
MPN:
LC1D2583E7
Condition:
New
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Width:
45 mm
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Contactor Application:
resistive load
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Product Certifications:
GOST || CSA || LROS (Lloyds register of shipping) || DNV || RINA || GL || BV || CCC || UL || UKCA
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Operating Time:
12...22 ms closing || 4...19 ms opening
Insulation Resistance:
> 10 MOhm for Signaling circuit
Circularity Profile:
ENVEOLI110229EN
[Ie] Rated Operational Current:
40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Sustainable Offer Status:
Green Premium product
Heat Dissipation:
2-3 W at 50/60 Hz
Protective Cover:
with
Eu Rohs Directive:
Compliant
Pole Contact Composition:
2 NO + 2 NC
Depth:
99 mm
Protective Treatment:
THIEC 60068-2-30
Connections - Terminals:
control circuit: spring terminals 1 2.5-2.5 mm² - cable stiffness: flexible without cable end || control circuit: spring terminals 2 2.5-2.5 mm² - cable stiffness: flexible without cable end || power circuit: spring terminals 1 10-10 mm² - cable s
Electrical Durability:
1.4 Mcycles 40 A AC-1 <= 440 V
Coil Technology:
without built-in suppressor module
Compatibility Code:
LC1D
Auxiliary Contact Composition:
1 NO + 1 NC
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
[Icw] Rated Short-Time Withstand Current:
240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Net Weight:
0.425 kg
Device Short Name:
LC1D
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Pvc Free:
Yes
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
Control Circuit Type:
AC 50/60 Hz
Weight:
0.425 kg
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
Range Of Product:
TeSys Deca
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
[Uc] Control Circuit Voltage:
48 V AC 50/60 Hz
Minimum Switching Current:
5 mA for Signaling circuit
Environmental Disclosure:
ENVPEP110229EN
Country of Origin:
France
Rated Breaking Capacity:
450 A at 440 V for power circuit conforming to IEC 60947
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
$256.25

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose