Schneider Electric LC1D258D7 IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 2 NO and 2 NC, 42VAC 50/60Hz coil, open style
Schneider Electric
$246.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 42 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 1.8 N.m screw clamps terminals flat Ø 6 mm || po
- Compatibility Code:
- LC1D
- Net Weight:
- 0.425 kg
- Country of Origin:
- Indonesia
- Mechanical Durability:
- 15 Mcycles
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Heat Dissipation:
- 2-3 W at 50/60 Hz
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-60°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz
- Sustainable Offer Status:
- Green Premium product
- Overvoltage Category:
- III
- [Icw] Rated Short-Time Withstand Current:
- 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Height:
- 91 mm
- Rohs Exemption Information:
- Yes
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Signaling Circuit Frequency:
- 25...400 Hz
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Device Short Name:
- LC1D
- Product Or Component Type:
- contactor
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
- Depth:
- 99 mm
- Standards:
- EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Flame Retardance:
- V1 conforming to UL 94
- Pollution Degree:
- 3
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Width:
- 45 mm
- Protective Cover:
- with
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Power Dissipation Per Pole:
- 3.2 W AC-1
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
- [Ie] Rated Operational Current:
- 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Circularity Profile:
- ENVEOLI110229EN
- Protective Treatment:
- THIEC 60068-2-30
- Rated Breaking Capacity:
- 450 A at 440 V for power circuit conforming to IEC 60947
- Range Of Product:
- TeSys Deca
- Contactor Application:
- resistive load
- [Uc] Control Circuit Voltage:
- 42 V AC 50/60 Hz
- Product Certifications:
- UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
- Poles Description:
- 4P
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1