Schneider Electric LC1D258ED IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 2 NO and 2 NC, 48VDC coil, open style
Schneider Electric
$255.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 48 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Poles Description:
- 4P
- Control Circuit Voltage Limits:
- 0.1...0.25 Uc -40-60°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC
- Depth:
- 107 mm
- Weight:
- 0.585 kg
- Eu Rohs Directive:
- Compliant with Exemptions
- Height:
- 91 mm
- Circularity Profile:
- ENVEOLI1102030EN
- Overvoltage Category:
- III
- Operating Time:
- 63±15 % ms closing || 20±20 % ms opening
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Pollution Degree:
- 3
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz
- Protective Treatment:
- THIEC 60068-2-30
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Mounting Support:
- rail || plate
- Time Constant:
- 28 ms
- Pole Contact Composition:
- 2 NO + 2 NC
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Environmental Disclosure:
- ENVPEP110230EN
- Contactor Application:
- resistive load
- [Uc] Control Circuit Voltage:
- 48 V DC
- Hold-In Power Consumption In W:
- 5.4-5.4 W 20°C
- [Icw] Rated Short-Time Withstand Current:
- 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Inrush Power In W:
- 5.4-5.4 W 20°C)
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Compatibility Code:
- LC1D
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Power Dissipation Per Pole:
- 3.2 W AC-1
- Device Short Name:
- LC1D
- Fire Resistance:
- 850°C IEC 60695-2-1
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Mechanical Durability:
- 30 Mcycles
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Net Weight:
- 0.585 kg
- Range Of Product:
- TeSys Deca
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Signaling Circuit Frequency:
- 25...400 Hz
- Product Certifications:
- UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Rohs Exemption Information:
- Yes