Schneider Electric LC1D258GD IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 2 NO and 2 NC, 125VDC coil, open style
Schneider Electric
$255.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
- Rohs Exemption Information:
- Yes
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
- [Ie] Rated Operational Current:
- 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Rated Breaking Capacity:
- 450 A at 440 V for power circuit conforming to IEC 60947
- Overvoltage Category:
- III
- Eu Rohs Directive:
- Compliant with Exemptions
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Flame Retardance:
- V1 conforming to UL 94
- Protective Treatment:
- THIEC 60068-2-30
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Control Circuit Type:
- DC standard
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Product Certifications:
- UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
- Contactor Application:
- resistive load
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Height:
- 91 mm
- Average Impedance:
- 2 mOhm - Ith 40 A 50 Hz for power circuit
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Pvc Free:
- Yes
- Control Circuit Voltage Limits:
- 0.1...0.25 Uc -40-60°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC
- Depth:
- 107 mm
- Protective Cover:
- with
- Device Short Name:
- LC1D
- [Icw] Rated Short-Time Withstand Current:
- 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- Weight:
- 0.585 kg
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Standards:
- EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Mechanical Durability:
- 30 Mcycles
- Mercury Free:
- Yes
- Connections - Terminals:
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
- Net Weight:
- 0.585 kg
- Compatibility Code:
- LC1D
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Environmental Disclosure:
- ENVPEP110230EN
- Sustainable Offer Status:
- Green Premium product
- Time Constant:
- 28 ms
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
- Operating Time:
- 63±15 % ms closing || 20±20 % ms opening
- Range Of Product:
- TeSys Deca