Schneider Electric LC1D258U7 IEC contactor, TeSys Deca, nonreversing, 40A resistive, 4 pole, 2 NO and 2 NC, 240VAC coil, open style
Schneider Electric
$246.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 240 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Range Of Product:
- TeSys Deca
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- [Icw] Rated Short-Time Withstand Current:
- 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Pvc Free:
- Yes
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Mounting Support:
- plate || rail
- [Ie] Rated Operational Current:
- 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Mechanical Durability:
- 15 Mcycles
- Connections - Terminals:
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
- Signaling Circuit Frequency:
- 25...400 Hz
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4
- Contactor Application:
- resistive load
- Environmental Disclosure:
- ENVPEP110229EN
- Fire Resistance:
- 850°C IEC 60695-2-1
- Protective Treatment:
- THIEC 60068-2-30
- Eu Rohs Directive:
- Compliant
- Net Weight:
- 0.425 kg
- Compatibility Code:
- LC1D
- Flame Retardance:
- V1 conforming to UL 94
- Device Short Name:
- LC1D
- Rated Breaking Capacity:
- 450 A at 440 V for power circuit conforming to IEC 60947
- Heat Dissipation:
- 2-3 W at 50/60 Hz
- Width:
- 45 mm
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Poles Description:
- 4P
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Overvoltage Category:
- III
- Warranty:
- 18 months
- Depth:
- 99 mm
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Control Circuit Type:
- AC 50/60 Hz
- Protective Cover:
- with
- Product Certifications:
- UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Average Impedance:
- 2 mOhm - Ith 40 A 50 Hz for power circuit
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-60°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Sustainable Offer Status:
- Green Premium product
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Pole Contact Composition:
- 2 NO + 2 NC
- Electrical Durability:
- 1.4 Mcycles 40 A AC-1 <= 440 V
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- [Uc] Control Circuit Voltage:
- 240 V AC 50/60 Hz
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Height:
- 91 mm