Schneider Electric

Schneider Electric LC1D25B7 IEC contactor, TeSys Deca, nonreversing, 25A, 15HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D25B7
MPN:
LC1D25B7
Condition:
New
Circularity Profile:
ENVEOLI110229EN
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Electrical Durability:
1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
Utilisation Category:
AC-1 || AC-3 || AC-4 || AC-3e
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
Compatibility Code:
LC1D
Sustainable Offer Status:
Green Premium product
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Pollution Degree:
3
Overvoltage Category:
III
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Operating Time:
12...22 ms closing || 4...19 ms opening
Protective Cover:
with
Coil Technology:
without built-in suppressor module
Mounting Support:
plate || rail
Maximum Horse Power Rating:
3 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 115 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 15 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 20 hp at 575/600 V AC 50/60 Hz for 3 phase
Protective Treatment:
THIEC 60068-2-30
Signaling Circuit Frequency:
25...400 Hz
Operating Altitude:
0...9842.52 ft (0...3000 m)
Mechanical Durability:
15 Mcycles
Poles Description:
3P
Eu Rohs Directive:
Compliant
Range Of Product:
TeSys Deca
Device Short Name:
LC1D
Motor Power Kw:
5.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 11 kW at 380...400 V AC 50/60 Hz (AC-3) || 11 kW at 415...440 V AC 50/60 Hz (AC-3) || 15 kW at 500 V AC 50/60 Hz (AC-3) || 15 kW at 660...690 V AC 50/60 Hz (AC-3) || 5.5 kW at 400 V AC 50/60 Hz (AC-4) || 5.
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application:
resistive load || motor control
Flame Retardance:
V1 conforming to UL 94
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Maximum Operating Rate:
3600 cyc/h 60°C
Control Circuit Type:
AC 50/60 Hz standard
Pole Contact Composition:
3 NO
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
Environmental Disclosure:
ENVPEP110229EN
Country of Origin:
France
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current:
5 mA for Signaling circuit
Ip Degree Of Protection:
IP20 front face IEC 60529
[Uc] Control Circuit Voltage:
24 V AC 50/60 Hz
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
[Icw] Rated Short-Time Withstand Current:
240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Weight:
0.37 kg
Power Dissipation Per Pole:
3.2 W AC-1 || 1.25 W AC-3 || 1.25 W AC-3e
$181.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200-208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 60A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose