Schneider Electric LC1D25LE7 IEC contactor, TeSys Deca, nonreversing, 25A, 15HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 208VAC 50/60Hz coil, open
Schneider Electric
$181.20
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200-208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 60A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 208 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Width:
- 45 mm
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
- Fire Resistance:
- 850°C IEC 60695-2-1
- Compatibility Code:
- LC1D
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
- Poles Description:
- 3P
- Motor Power Kw:
- 5.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 11 kW at 380...400 V AC 50/60 Hz (AC-3) || 11 kW at 415...440 V AC 50/60 Hz (AC-3) || 15 kW at 500 V AC 50/60 Hz (AC-3) || 15 kW at 660...690 V AC 50/60 Hz (AC-3) || 5.5 kW at 400 V AC 50/60 Hz (AC-4) || 5.
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Average Impedance:
- 2 mOhm - Ith 40 A 50 Hz for power circuit
- Protective Cover:
- with
- Connections - Terminals:
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
- Pole Contact Composition:
- 3 NO
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Protective Treatment:
- THIEC 60068-2-30
- Power Dissipation Per Pole:
- 3.2 W AC-1 || 1.25 W AC-3 || 1.25 W AC-3e
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Product Certifications:
- CSA || RINA || UL || GOST || DNV || BV || GL || CCC || LROS (Lloyds register of shipping) || UKCA
- Environmental Disclosure:
- ENVPEP110229EN
- Mounting Support:
- rail || plate
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Eu Rohs Directive:
- Compliant
- Signaling Circuit Frequency:
- 25...400 Hz
- Rated Breaking Capacity:
- 450 A at 440 V for power circuit conforming to IEC 60947
- Device Short Name:
- LC1D
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Mechanical Durability:
- 15 Mcycles
- Coil Technology:
- without built-in suppressor module
- Depth:
- 92 mm
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Product Or Component Type:
- contactor
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Contactor Application:
- resistive load || motor control
- Electrical Durability:
- 1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
- Maximum Horse Power Rating:
- 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 115 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 15 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 20 hp at 575/600 V AC 50/60 Hz for 3 phase
- Sustainable Offer Status:
- Green Premium product
- Pvc Free:
- Yes
- Overvoltage Category:
- III
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- [Icw] Rated Short-Time Withstand Current:
- 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Circularity Profile:
- ENVEOLI110229EN
- Minimum Switching Current:
- 5 mA for Signaling circuit