Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
Compatibility Code:
LC1D
Rohs Exemption Information:
Yes
Depth:
92 mm
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Warranty:
18 months
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Circularity Profile:
ENVEOLI110229EN
Operating Altitude:
0...9842.52 ft (0...3000 m)
Range Of Product:
TeSys Deca
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Environmental Disclosure:
ENVPEP110229EN
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Height:
85 mm
Mounting Support:
plate || rail
Mechanical Durability:
15 Mcycles
Operating Time:
12...22 ms closing || 4...19 ms opening
Pvc Free:
Yes
Insulation Resistance:
> 10 MOhm for Signaling circuit
Minimum Switching Current:
5 mA for Signaling circuit
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
Protective Cover:
with
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Coil Technology:
without built-in suppressor module
[Icw] Rated Short-Time Withstand Current:
240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Weight:
0.37 kg
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
Auxiliary Contact Composition:
1 NO + 1 NC
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
Fire Resistance:
850°C IEC 60695-2-1
Maximum Operating Rate:
3600 cyc/h 60°C
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
Utilisation Category:
AC-3 || AC-4 || AC-1 || AC-3e
Overvoltage Category:
III
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Pole Contact Composition:
3 NO
Sustainable Offer Status:
Green Premium product
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Protective Treatment:
THIEC 60068-2-30
Maximum Horse Power Rating:
3 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 115 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 15 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 20 hp at 575/600 V AC 50/60 Hz for 3 phase
Country of Origin:
France
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Motor Power Kw:
5.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 11 kW at 380...400 V AC 50/60 Hz (AC-3) || 11 kW at 415...440 V AC 50/60 Hz (AC-3) || 15 kW at 500 V AC 50/60 Hz (AC-3) || 15 kW at 660...690 V AC 50/60 Hz (AC-3) || 5.5 kW at 400 V AC 50/60 Hz (AC-4) || 5.
$181.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200-208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 60A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 400 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.