Schneider Electric

Schneider Electric LC1D25X7 IEC contactor, TeSys Deca, nonreversing, 25A, 15HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 600VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D25X7
MPN:
LC1D25X7
Condition:
New
Protective Cover:
with
Product Certifications:
CCC || UL || GL || RINA || DNV || LROS (Lloyds register of shipping) || CSA || GOST || BV || UKCA
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
Overvoltage Category:
III
Power Dissipation Per Pole:
3.2 W AC-1 || 1.25 W AC-3 || 1.25 W AC-3e
[Icw] Rated Short-Time Withstand Current:
240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
[Uc] Control Circuit Voltage:
600 V AC 50/60 Hz
Width:
45 mm
Utilisation Category:
AC-4 || AC-3 || AC-1 || AC-3e
Circularity Profile:
ENVEOLI110229EN
Pole Contact Composition:
3 NO
Weight:
0.37 kg
Insulation Resistance:
> 10 MOhm for Signaling circuit
Compatibility Code:
LC1D
Pvc Free:
Yes
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Device Short Name:
LC1D
Operating Altitude:
0...9842.52 ft (0...3000 m)
Flame Retardance:
V1 conforming to UL 94
Motor Power Kw:
5.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 11 kW at 380...400 V AC 50/60 Hz (AC-3) || 11 kW at 415...440 V AC 50/60 Hz (AC-3) || 15 kW at 500 V AC 50/60 Hz (AC-3) || 15 kW at 660...690 V AC 50/60 Hz (AC-3) || 5.5 kW at 400 V AC 50/60 Hz (AC-4) || 5.
Average Impedance:
2 mOhm - Ith 40 A 50 Hz for power circuit
Product Or Component Type:
contactor
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Pollution Degree:
3
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Auxiliary Contact Composition:
1 NO + 1 NC
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Minimum Switching Voltage:
17 V for Signaling circuit
Signaling Circuit Frequency:
25...400 Hz
Sustainable Offer Status:
Green Premium product
Fire Resistance:
850°C IEC 60695-2-1
Ip Degree Of Protection:
IP20 front face IEC 60529
Eu Rohs Directive:
Compliant
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Heat Dissipation:
2-3 W at 50/60 Hz
Range Of Product:
TeSys Deca
Minimum Switching Current:
5 mA for Signaling circuit
Protective Treatment:
THIEC 60068-2-30
Warranty:
18 months
Maximum Horse Power Rating:
3 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 115 V AC 50/60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 15 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 20 hp at 575/600 V AC 50/60 Hz for 3 phase
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Poles Description:
3P
Net Weight:
0.37 kg
$181.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200-208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 60A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 600 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose