Schneider Electric

Schneider Electric LC1D323P7 IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 230VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D323P7
MPN:
LC1D323P7
Condition:
New
Motor Power Kw:
7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Eu Rohs Directive:
Compliant
Protective Cover:
with
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
Overvoltage Category:
III
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pole Contact Composition:
3 NO
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Rohs Exemption Information:
Yes
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Heat Dissipation:
2-3 W at 50/60 Hz
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Sustainable Offer Status:
Green Premium product
Insulation Resistance:
> 10 MOhm for Signaling circuit
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
Product Or Component Type:
contactor
Minimum Switching Current:
5 mA for Signaling circuit
Operating Time:
12...22 ms closing || 4...19 ms opening
Signaling Circuit Frequency:
25...400 Hz
Contactor Application:
resistive load || motor control
Maximum Horse Power Rating:
2 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 20 hp at 460/480 V AC 50/60 Hz for 3 phase m
Depth:
92 mm
[Icw] Rated Short-Time Withstand Current:
260 A 40°C - 10 s for power circuit || 430 A 40°C - 1 s for power circuit || 60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Net Weight:
0.375 kg
Pollution Degree:
3
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Ip Degree Of Protection:
IP20 front face IEC 60529
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Product Certifications:
DNV || GL || LROS (Lloyds register of shipping) || UL || CCC || RINA || CSA || BV || GOST || UKCA
Range Of Product:
TeSys Deca
[Ie] Rated Operational Current:
32 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Coil Technology:
without built-in suppressor module
Protective Treatment:
THIEC 60068-2-30
Flame Retardance:
V1 conforming to UL 94
Country of Origin:
Indonesia
Mounting Support:
rail || plate
Width:
45 mm
Warranty:
18 months
[Uc] Control Circuit Voltage:
230 V AC 50/60 Hz
$206.40

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.90 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.83 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose