Schneider Electric

Schneider Electric LC1D326BD IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D326BD
MPN:
LC1D326BD
Condition:
New
[Uc] Control Circuit Voltage:
24 V DC
Minimum Switching Voltage:
17 V for Signaling circuit
Flame Retardance:
V1 conforming to UL 94
Signaling Circuit Frequency:
25...400 Hz
Warranty:
18 months
Mounting Support:
rail || plate
Control Circuit Type:
DC standard
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Rohs Exemption Information:
Yes
Mercury Free:
Yes
Pvc Free:
Yes
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Weight:
0.535 kg
[Icw] Rated Short-Time Withstand Current:
260 A 40°C - 10 s for power circuit || 430 A 40°C - 1 s for power circuit || 60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Circularity Profile:
ENVEOLI1102030EN
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Maximum Operating Rate:
3600 cyc/h 60°C
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
Height:
85 mm
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Time Constant:
28 ms
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 10 mm
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
Maximum Horse Power Rating:
2 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 20 hp at 460/480 V AC 50/60 Hz for 3 phase m
Compatibility Code:
LC1D
Ip Degree Of Protection:
IP20 front face IEC 60529
Protective Cover:
with
Device Short Name:
LC1D
Depth:
101 mm
Pollution Degree:
3
Electrical Durability:
1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Net Weight:
0.535 kg
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Operating Altitude:
0...9842.52 ft (0...3000 m)
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current:
5 mA for Signaling circuit
Width:
45 mm
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Eu Rohs Directive:
Compliant with Exemptions
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4 |
Inrush Power In W:
5.4-5.4 W 20°C)
Sustainable Offer Status:
Green Premium product
$215.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose