Schneider Electric

Schneider Electric LC1D326F7 IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 110VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D326F7
MPN:
LC1D326F7
Condition:
New
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Auxiliary Contact Composition:
1 NO + 1 NC
Signaling Circuit Frequency:
25...400 Hz
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Eu Rohs Directive:
Compliant
Operating Time:
12...22 ms closing || 4...19 ms opening
Flame Retardance:
V1 conforming to UL 94
Fire Resistance:
850°C IEC 60695-2-1
Minimum Switching Voltage:
17 V for Signaling circuit
Pollution Degree:
3
[Icw] Rated Short-Time Withstand Current:
260 A 40°C - 10 s for power circuit || 430 A 40°C - 1 s for power circuit || 60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4 |
Range Of Product:
TeSys Deca
Maximum Horse Power Rating:
2 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 20 hp at 460/480 V AC 50/60 Hz for 3 phase m
Device Short Name:
LC1D
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Depth:
92 mm
Product Or Component Type:
contactor
Overvoltage Category:
III
Maximum Operating Rate:
3600 cyc/h 60°C
Environmental Disclosure:
ENVPEP110229EN
Motor Power Kw:
7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
Warranty:
18 months
Protective Treatment:
THIEC 60068-2-30
Pole Contact Composition:
3 NO
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Insulation Resistance:
> 10 MOhm for Signaling circuit
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 10 mm
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Power Dissipation Per Pole:
2 W AC-3 || 5 W AC-1 || 2 W AC-3e
Country of Origin:
Indonesia
Mechanical Durability:
15 Mcycles
Circularity Profile:
ENVEOLI110229EN
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Net Weight:
0.375 kg
Mounting Support:
rail || plate
Height:
85 mm
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
Contactor Application:
resistive load || motor control
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Uc] Control Circuit Voltage:
110 V AC 50/60 Hz
Control Circuit Type:
AC 50/60 Hz
Weight:
0.375 kg
$206.40

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.90 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.83 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.