Schneider Electric

Schneider Electric LC1D326FD IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 110VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D326FD
MPN:
LC1D326FD
Condition:
New
Minimum Switching Current:
5 mA for Signaling circuit
Power Dissipation Per Pole:
2 W AC-3 || 5 W AC-1 || 2 W AC-3e
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Insulation Resistance:
> 10 MOhm for Signaling circuit
[Ie] Rated Operational Current:
32 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Weight:
0.535 kg
Time Constant:
28 ms
Motor Power Kw:
7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
Product Or Component Type:
contactor
Utilisation Category:
AC-3 || AC-1 || AC-4 || AC-3e
[Uc] Control Circuit Voltage:
110 V DC
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Maximum Operating Rate:
3600 cyc/h 60°C
Fire Resistance:
850°C IEC 60695-2-1
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Device Short Name:
LC1D
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
Pole Contact Composition:
3 NO
Inrush Power In W:
5.4-5.4 W 20°C)
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Poles Description:
3P
[Icw] Rated Short-Time Withstand Current:
260 A 40°C - 10 s for power circuit || 430 A 40°C - 1 s for power circuit || 60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 10 mm
Mechanical Durability:
30 Mcycles
Mercury Free:
Yes
Height:
85 mm
Signaling Circuit Frequency:
25...400 Hz
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Mounting Support:
rail || plate
Operating Altitude:
0...9842.52 ft (0...3000 m)
Compatibility Code:
LC1D
Contactor Application:
resistive load || motor control
Overvoltage Category:
III
Minimum Switching Voltage:
17 V for Signaling circuit
Rohs Exemption Information:
Yes
Net Weight:
0.535 kg
Pollution Degree:
3
Electrical Durability:
1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4 |
Circularity Profile:
ENVEOLI1102030EN
Country of Origin:
Indonesia
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Product Certifications:
UL || GL || BV || CCC || DNV || CSA || RINA || GOST || LROS (Lloyds register of shipping) || UKCA
Eu Rohs Directive:
Compliant with Exemptions
Operating Time:
63±15 % ms closing || 20±20 % ms opening
$215.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose