Schneider Electric

Schneider Electric LC1D326GD IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 125VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D326GD
MPN:
LC1D326GD
Condition:
New
Control Circuit Type:
DC standard
Operating Time:
63±15 % ms closing || 20±20 % ms opening
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 10 mm
Mounting Support:
plate || rail
Range Of Product:
TeSys Deca
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Height:
85 mm
Maximum Operating Rate:
3600 cyc/h 60°C
Signaling Circuit Frequency:
25...400 Hz
Fire Resistance:
850°C IEC 60695-2-1
Width:
45 mm
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile:
ENVEOLI1102030EN
Rohs Exemption Information:
Yes
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
Time Constant:
28 ms
Minimum Switching Current:
5 mA for Signaling circuit
Sustainable Offer Status:
Green Premium product
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Mechanical Durability:
30 Mcycles
Maximum Horse Power Rating:
2 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 20 hp at 460/480 V AC 50/60 Hz for 3 phase m
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Environmental Disclosure:
ENVPEP110230EN
Compatibility Code:
LC1D
Net Weight:
0.535 kg
Device Short Name:
LC1D
Overvoltage Category:
III
Country of Origin:
France
Minimum Switching Voltage:
17 V for Signaling circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Utilisation Category:
AC-1 || AC-4 || AC-3 || AC-3e
[Ie] Rated Operational Current:
32 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Product Certifications:
RINA || BV || CSA || LROS (Lloyds register of shipping) || UL || GOST || DNV || GL || CCC || UKCA
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
Tightening Torque:
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4 |
Protective Treatment:
THIEC 60068-2-30
Motor Power Kw:
7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
Flame Retardance:
V1 conforming to UL 94
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Pollution Degree:
3
[Icw] Rated Short-Time Withstand Current:
260 A 40°C - 10 s for power circuit || 430 A 40°C - 1 s for power circuit || 60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Operating Altitude:
0...9842.52 ft (0...3000 m)
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Inrush Power In W:
5.4-5.4 W 20°C)
Electrical Durability:
1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
Power Dissipation Per Pole:
2 W AC-3 || 5 W AC-1 || 2 W AC-3e
$268.75

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose