Schneider Electric

Schneider Electric LC1D32BNE IEC contactor, TeSys Deca Green, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24/60VAC/VDC coil, open

(No reviews yet) Write a Review
SKU:
LC1D32BNE
MPN:
LC1D32BNE
Condition:
New
Mercury Free:
Yes
[Uc] Control Circuit Voltage:
24...60 V AC 50/60 Hz || 24...60 V DC
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Fire Resistance:
850°C IEC 60695-2-1
Auxiliary Contact Composition:
1 NO + 1 NC
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || power
Electrical Durability:
2.1 Mcycles 29 A AC-3 <= 440 V || 0.9 Mcycles 50 A AC-1 <= 440 V || 2.1 Mcycles 29 A AC-3e <= 440 V
Mechanical Durability:
15 Mcycles
Utilisation Category:
AC-1 || AC-3 || AC-3e
Weight:
0.438 kg
Product Certifications:
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Control Circuit Type:
AC/DC 50/60 Hz AC/DC electronic
Halogen Content Performance:
Halogen free plastic parts & cables product
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms for Signaling circuit || 60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 260 A 40°C - 10 s for power circuit || 430 A 40°C - 1
[Ie] Rated Operational Current:
32 A (at <60°C) at <= 440 V AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC-1 for power circuit || 32 A (at <60°C) at <= 440 V AC-3e for power circuit
Insulation Resistance:
> 10 MOhm for Signaling circuit
Maximum Operating Rate:
3600 cyc/h 60°C
Net Weight:
0.438 kg
Heat Dissipation:
0.6-0.6 W at 50/60 Hz
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Depth:
92 mm
Maximum Horse Power Rating:
2 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 20 hp at 460/480 V AC 50/60 Hz for 3 phase m
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Control Circuit Voltage Limits:
<= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC || 0.8...1.1 Uc -40-60°C operational DC || 1...1.1 Uc 60-70°C operational AC/DC
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Minimum Switching Current:
5 mA for Signaling circuit
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Country of Origin:
France
Warranty:
18 months
Motor Power Kw:
7.5 kW at 220...230 V AC 50 Hz (AC-3) || 15 kW at 380...400 V AC 50 Hz (AC-3) || 15 kW at 415 V AC 50 Hz (AC-3) || 15 kW at 440 V AC 50 Hz (AC-3) || 18.5 kW at 500 V AC 50 Hz (AC-3) || 18.5 kW at 660...690 V AC 50 Hz (AC-3) || 7.5 kW at 220...230 V A
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Protective Cover:
with
Poles Description:
3P
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-1
Minimum Switching Voltage:
17 V for Signaling circuit
Inrush Power In W:
14-14 W 20°C)
Flame Retardance:
V1 conforming to UL 94
Contactor Application:
motor control || resistive load
Eu Rohs Directive:
Compliant with Exemptions
Coil Technology:
built-in bidirectional peak limiting
Hold-In Power Consumption In Va:
0.9-0.9 VA 50/60 Hz (at 20°C)
Overvoltage Category:
III
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
$86.00

Description

TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 24-60V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.97 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.