Schneider Electric

Schneider Electric LC1D32FE7 IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 115VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D32FE7
MPN:
LC1D32FE7
Condition:
New
Overvoltage Category:
III
Rohs Exemption Information:
Yes
Pole Contact Composition:
3 NO
Minimum Switching Voltage:
17 V for Signaling circuit
Operating Altitude:
0...9842.52 ft (0...3000 m)
Width:
45 mm
Maximum Horse Power Rating:
2 hp at 115 V AC 50/60 Hz for 1 phase motors || 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 20 hp at 460/480 V AC 50/60 Hz for 3 phase m
Device Short Name:
LC1D
Compatibility Code:
LC1D
[Uc] Control Circuit Voltage:
115 V AC 50/60 Hz
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Operating Time:
12...22 ms closing || 4...19 ms opening
Maximum Operating Rate:
3600 cyc/h 60°C
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Fire Resistance:
850°C IEC 60695-2-1
Country of Origin:
France
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Eu Rohs Directive:
Compliant
Protective Cover:
with
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Flame Retardance:
V1 conforming to UL 94
Poles Description:
3P
Product Or Component Type:
contactor
Motor Power Kw:
7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
[Icw] Rated Short-Time Withstand Current:
260 A 40°C - 10 s for power circuit || 430 A 40°C - 1 s for power circuit || 60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Contactor Application:
resistive load || motor control
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Auxiliary Contact Composition:
1 NO + 1 NC
Net Weight:
0.375 kg
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Signaling Circuit Frequency:
25...400 Hz
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Ip Degree Of Protection:
IP20 front face IEC 60529
Electrical Durability:
1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 32 A AC-3e <= 440 V
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
Protective Treatment:
THIEC 60068-2-30
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Warranty:
18 months
Coil Technology:
without built-in suppressor module
Sustainable Offer Status:
Green Premium product
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Depth:
92 mm
[Ie] Rated Operational Current:
32 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-3e for power circuit
$206.40

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 115 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.83 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose