Schneider Electric LC1D32JD IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 12VDC coil, open style
Schneider Electric
$215.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Protective Treatment:
- THIEC 60068-2-30
- Circularity Profile:
- ENVEOLI1102030EN
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Range Of Product:
- TeSys Deca
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Sustainable Offer Status:
- Green Premium product
- Inrush Power In W:
- 5.4-5.4 W 20°C)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Mercury Free:
- Yes
- Country of Origin:
- Indonesia
- Operating Time:
- 63±15 % ms closing || 20±20 % ms opening
- Fire Resistance:
- 850°C IEC 60695-2-1
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Utilisation Category:
- AC-1 || AC-3 || AC-4 || AC-3e
- Rated Breaking Capacity:
- 550 A at 440 V for power circuit conforming to IEC 60947
- Control Circuit Voltage Limits:
- 0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Weight:
- 0.535 kg
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- [Uc] Control Circuit Voltage:
- 12 V DC
- Warranty:
- 18 months
- Rohs Exemption Information:
- Yes
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Contactor Application:
- resistive load || motor control
- Time Constant:
- 28 ms
- Average Impedance:
- 2 mOhm - Ith 50 A 50 Hz for power circuit
- Pole Contact Composition:
- 3 NO
- Power Dissipation Per Pole:
- 2 W AC-3 || 5 W AC-1 || 2 W AC-3e
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree:
- 3
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Flame Retardance:
- V1 conforming to UL 94
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Eu Rohs Directive:
- Compliant with Exemptions
- Connections - Terminals:
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
- Control Circuit Type:
- DC standard
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Hold-In Power Consumption In W:
- 5.4-5.4 W 20°C
- Electrical Durability:
- 1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 32 A AC-3e <= 440 V
- Motor Power Kw:
- 7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact