Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
Control Circuit Voltage Limits:
0.1...0.3 Uc -40-70°C drop-out DC || 0.8...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Eu Rohs Directive:
Compliant with Exemptions
Power Dissipation Per Pole:
2 W AC-3 || 5 W AC-1 || 2 W AC-3e
Maximum Operating Rate:
3600 cyc/h 60°C
Connections - Terminals:
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² -
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
Environmental Disclosure:
ENVPEP110230EN
Ip Degree Of Protection:
IP20 front face IEC 60529
Motor Power Kw:
7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
Warranty:
18 months
Auxiliary Contact Composition:
1 NO + 1 NC
Contactor Application:
motor control || resistive load
Product Or Component Type:
contactor
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Overvoltage Category:
III
Protective Treatment:
THIEC 60068-2-30
Control Circuit Type:
DC low consumption
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Poles Description:
3P
Compatibility Code:
LC1D
Hold-In Power Consumption In W:
2.4-2.4 W 20°C
Mechanical Durability:
30 Mcycles
Fire Resistance:
850°C IEC 60695-2-1
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Operating Altitude:
0...9842.52 ft (0...3000 m)
Mounting Support:
rail || plate
Depth:
101 mm
Range Of Product:
TeSys Deca
Pvc Free:
Yes
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Protective Cover:
with
Rohs Exemption Information:
Yes
[Ie] Rated Operational Current:
32 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Time Constant:
40 ms
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Flame Retardance:
V1 conforming to UL 94
Insulation Resistance:
> 10 MOhm for Signaling circuit
Electrical Durability:
1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 32 A AC-3e <= 440 V
[Icw] Rated Short-Time Withstand Current:
260 A 40°C - 10 s for power circuit || 430 A 40°C - 1 s for power circuit || 60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Weight:
0.535 kg
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Inrush Power In W:
2.4-2.4 W 20°C)
$258.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumption 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.