Schneider Electric

Schneider Electric LC1D32P7 IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 230VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D32P7
MPN:
LC1D32P7
Condition:
New
Depth:
92 mm
Pvc Free:
Yes
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
Range:
TeSys || TeSys Deca
Insulation Resistance:
> 10 MOhm for Signaling circuit
Contactor Application:
resistive load || motor control
Pollution Degree:
3
Compatibility Code:
LC1D
Control Circuit Type:
AC 50/60 Hz standard
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Width:
45 mm
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Environmental Disclosure:
ENVPEP110229EN
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Rohs Exemption Information:
Yes
Eu Rohs Directive:
Compliant
Electrical Durability:
1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 32 A AC-3e <= 440 V
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Net Weight:
0.375 kg
Flame Retardance:
V1 conforming to UL 94
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
Product Or Component Type:
contactor
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
[Icw] Rated Short-Time Withstand Current:
60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 260 A 40°C - 10 s for power circuit || 430 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Maximum Operating Rate:
3600 cyc/h 60°C
Signaling Circuit Frequency:
25...400 Hz
Auxiliary Contact Composition:
1 NO + 1 NC
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Power Dissipation Per Pole:
2 W AC-3 || 5 W AC-1 || 2 W AC-3e
Product Certifications:
DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
Mechanical Durability:
15 Mcycles
Operating Altitude:
0...9842.52 ft (0...3000 m)
Sustainable Offer Status:
Green Premium product
Device Short Name:
LC1D
Minimum Switching Voltage:
17 V for Signaling circuit
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
[Ie] Rated Operational Current:
32 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Fire Resistance:
850°C IEC 60695-2-1
Protective Treatment:
THIEC 60068-2-30
Height:
85 mm
Mounting Support:
rail || plate
Motor Power Kw:
7.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 15 kW at 380...400 V AC 50/60 Hz (AC-3) || 15 kW at 415...440 V AC 50/60 Hz (AC-3) || 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
Poles Description:
3P
Warranty:
18 months
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
$206.40

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.83 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose