Schneider Electric

Schneider Electric LC1D38BD IEC contactor, TeSys Deca, nonreversing, 38A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style

(No reviews yet) Write a Review
SKU:
LC1D38BD
MPN:
LC1D38BD
Condition:
New
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Pvc Free:
Yes
Country of Origin:
Indonesia
Environmental Disclosure:
ENVPEP110230EN
Maximum Operating Rate:
3600 cyc/h 60°C
Signaling Circuit Frequency:
25...400 Hz
Product Or Component Type:
contactor
Product Certifications:
DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
Sustainable Offer Status:
Green Premium product
Mechanical Durability:
30 Mcycles
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Net Weight:
0.54 kg
Pollution Degree:
3
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Eu Rohs Directive:
Compliant with Exemptions
Insulation Resistance:
> 10 MOhm for Signaling circuit
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
Contactor Application:
resistive load || motor control
Device Short Name:
LC1D
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Control Circuit Type:
DC standard
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Protective Cover:
with
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
Maximum Horse Power Rating:
10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 240 V AC 50/60 Hz for 1 phase motors || 20 hp at 480 V AC 50/60 Hz for 3 phase motors || 25 hp at 600 V AC 50/60 Hz for 3 phase motors
Flame Retardance:
V1 conforming to UL 94
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Operating Time:
20±20 % ms opening || 63±15 % ms closing
Power Dissipation Per Pole:
5 W AC-1 || 3 W AC-3 || 3 W AC-3e
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Warranty:
18 months
Electrical Durability:
1.4 Mcycles 50 A AC-1 <= 440 V || 1.4 Mcycles 38 A AC-3 <= 440 V || 1.4 Mcycles 38 A AC-3e <= 440 V
Poles Description:
3P
[Uc] Control Circuit Voltage:
24 V DC
Auxiliary Contact Composition:
1 NO + 1 NC
Mounting Support:
plate || rail
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Operating Altitude:
0...9842.52 ft (0...3000 m)
Range Of Product:
TeSys Deca
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
$241.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose