Schneider Electric LC1D38BL IEC contactor, TeSys Deca, nonreversing, 38A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, low consumption 24VDC coil
Schneider Electric
$289.20
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Rated Breaking Capacity:
- 550 A at 440 V for power circuit conforming to IEC 60947
- Fire Resistance:
- 850°C IEC 60695-2-1
- Electrical Durability:
- 1.4 Mcycles 50 A AC-1 <= 440 V || 1.4 Mcycles 38 A AC-3 <= 440 V || 1.4 Mcycles 38 A AC-3e <= 440 V
- Country of Origin:
- Singapore
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Device Short Name:
- LC1D
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Depth:
- 101 mm
- Time Constant:
- 40 ms
- Sustainable Offer Status:
- Green Premium product
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Protective Cover:
- with
- Height:
- 85 mm
- Motor Power Kw:
- 18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) || 18.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 9 kW at 220...230 V AC 50/60 Hz (AC-3) || 18.5 kW at 415...440 V AC 50/60 Hz (AC-3)
- Poles Description:
- 3P
- Pvc Free:
- Yes
- Mechanical Durability:
- 30 Mcycles
- Compatibility Code:
- LC1D
- Circularity Profile:
- ENVEOLI1102030EN
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Range:
- TeSys || TeSys Deca
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Average Impedance:
- 2 mOhm - Ith 50 A 50 Hz for power circuit
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
- Mechanical Robustness:
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Control Circuit Type:
- DC low consumption
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- [Ie] Rated Operational Current:
- 50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 38 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 38 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- [Uc] Control Circuit Voltage:
- 24 V DC
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Range Of Product:
- TeSys Deca
- Operating Time:
- 77±15 % ms closing || 25±20 % ms opening
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Flame Retardance:
- V1 conforming to UL 94
- Pole Contact Composition:
- 3 NO
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Power Dissipation Per Pole:
- 5 W AC-1 || 3 W AC-3 || 3 W AC-3e
- Rohs Exemption Information:
- Yes
- Inrush Power In W:
- 2.4-2.4 W 20°C)
- Mounting Support:
- rail || plate
- Signaling Circuit Frequency:
- 25...400 Hz
- Warranty:
- 18 months
- Environmental Disclosure:
- ENVPEP110230EN
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Maximum Horse Power Rating:
- 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 240 V AC 50/60 Hz for 1 phase motors || 20 hp at 480 V AC 50/60 Hz for 3 phase motors || 25 hp at 600 V AC 50/60 Hz for 3 phase motors
- Protective Treatment:
- THIEC 60068-2-30