Schneider Electric

Schneider Electric LC1D38P7 IEC contactor, TeSys Deca, nonreversing, 38A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 230VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D38P7
MPN:
LC1D38P7
Condition:
New
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Net Weight:
0.38 kg
Pole Contact Composition:
3 NO
Device Short Name:
LC1D
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Control Circuit Type:
AC 50/60 Hz
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Eu Rohs Directive:
Compliant
Fire Resistance:
850°C IEC 60695-2-1
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Product Certifications:
DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
Power Dissipation Per Pole:
5 W AC-1 || 3 W AC-3 || 3 W AC-3e
Sustainable Offer Status:
Green Premium product
Overvoltage Category:
III
[Uc] Control Circuit Voltage:
230 V AC 50/60 Hz
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Operating Time:
4...19 ms opening || 12...22 ms closing
[Icw] Rated Short-Time Withstand Current:
60 A 40°C - 10 min for power circuit || 430 A 40°C - 1 s for power circuit || 150 A 40°C - 1 min for power circuit || 310 A 40°C - 10 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Mechanical Durability:
15 Mcycles
Heat Dissipation:
2-3 W at 50/60 Hz
Warranty:
18 months
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Poles Description:
3P
Weight:
0.38 kg
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
Circularity Profile:
ENVEOLI110229EN
Pollution Degree:
3
Flame Retardance:
V1 conforming to UL 94
Insulation Resistance:
> 10 MOhm for Signaling circuit
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
Range Of Product:
TeSys Deca
Ip Degree Of Protection:
IP20 front face IEC 60529
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Maximum Horse Power Rating:
10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 240 V AC 50/60 Hz for 1 phase motors || 20 hp at 480 V AC 50/60 Hz for 3 phase motors || 25 hp at 600 V AC 50/60 Hz for 3 phase motors
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Motor Power Kw:
18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) || 18.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 9 kW at 220...230 V AC 50/60 Hz (AC-3) || 18.5 kW at 415...440 V AC 50/60 Hz (AC-3)
Environmental Disclosure:
ENVPEP110229EN
Protective Cover:
with
Range:
TeSys || TeSys Deca
Depth:
92 mm
Country of Origin:
Indonesia
Rohs Exemption Information:
Yes
Coil Technology:
without built-in suppressor module
[Ie] Rated Operational Current:
50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 38 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 38 A (at <60°C) at <= 440 V AC AC-3e for power circuit
$231.60

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.84 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose