Schneider Electric

Schneider Electric LC1D38R7 IEC contactor, TeSys Deca, nonreversing, 38A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 440VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D38R7
MPN:
LC1D38R7
Condition:
New
Country of Origin:
Indonesia
Operating Time:
4...19 ms opening || 12...22 ms closing
Contactor Application:
motor control || resistive load
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Circularity Profile:
ENVEOLI110229EN
Protective Treatment:
THIEC 60068-2-30
Depth:
92 mm
Overvoltage Category:
III
Poles Description:
3P
Fire Resistance:
850°C IEC 60695-2-1
Rohs Exemption Information:
Yes
Mounting Support:
plate || rail
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
Range:
TeSys || TeSys Deca
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
Electrical Durability:
1.4 Mcycles 50 A AC-1 <= 440 V || 1.4 Mcycles 38 A AC-3 <= 440 V || 1.4 Mcycles 38 A AC-3e <= 440 V
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Ip Degree Of Protection:
IP20 front face IEC 60529
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
Operating Altitude:
0...9842.52 ft (0...3000 m)
Product Certifications:
DNV || GL || CCC || LROS (Lloyds register of shipping) || RINA || BV || GOST || UL || CSA || CB
Insulation Resistance:
> 10 MOhm for Signaling circuit
Pollution Degree:
3
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Compatibility Code:
LC1D
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure:
ENVPEP110229EN
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pvc Free:
Yes
Motor Power Kw:
18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) || 18.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 9 kW at 220...230 V AC 50/60 Hz (AC-3) || 18.5 kW at 415...440 V AC 50/60 Hz (AC-3)
Heat Dissipation:
2-3 W at 50/60 Hz
Pole Contact Composition:
3 NO
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Sustainable Offer Status:
Green Premium product
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Device Short Name:
LC1D
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Warranty:
18 months
Weight:
0.38 kg
$231.60

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 440 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.84 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose