TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 60A resistive load rating. Contactor is supplied with a 110 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 4.92 inches deep. It weighs 3.17 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc 60-60°C drop-out AC 50/60 Hz || 0.8...1.1 Uc 60-60°C operational AC 50 Hz || 0.85...1.1 Uc 60-60°C operational AC 60 Hz
- Connections - Terminals:
- control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable s
- Operating Altitude:
- 9842.52 ft (3000 m) without derating
- Minimum Switching Current:
- 5 mA for control circuit
- Weight:
- 1.44 kg
- Heat Dissipation:
- 4-5 W at 50/60 Hz for control circuit
- Fire Resistance:
- 850°C IEC 60695-2-1
- Depth:
- 125 mm
- Compatibility Code:
- LC1D
- Circularity Profile:
- N/A
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Ip Degree Of Protection:
- IP2X IEC 60529 || IP2X VDE 0106
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Pole Contact Composition:
- 4 NO
- Net Weight:
- 1.44 kg
- Average Impedance:
- 1.5 mOhm - Ith 60 A 50 Hz for power circuit
- Poles Description:
- 4P
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Protective Cover:
- with
- Coil Technology:
- without built-in bidirectional peak limiting diode suppressor
- Range Of Product:
- TeSys Deca
- [Ie] Rated Operational Current:
- 60 A (at <60°C) AC AC-1 for power circuit
- Toxic Heavy Metal Free:
- Yes
- Associated Fuse Rating:
- 10 A gG for control circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
- Hold-In Power Consumption In Va:
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
- [Ui] Rated Insulation Voltage:
- control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1
- Mercury Free:
- Yes
- Control Circuit Type:
- AC 50/60 Hz standard
- Warranty:
- 18 months
- Power Dissipation Per Pole:
- 5.4 W AC-1
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for control circuit || 60 A (at 60°C) for power circuit
- Minimum Switching Voltage:
- 17 V for control circuit
- Insulation Resistance:
- > 10 MOhm for control circuit
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz
- Environmental Disclosure:
- ENVPEP110205EN
- Irms Rated Making Capacity:
- 140 A AC for control circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
- Product Certifications:
- DNV || GOST || RINA || CSA || UL || LROS (Lloyds register of shipping) || CCC || BV || GL || UKCA
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Sustainable Offer Status:
- Green Premium product
- Mounting Support:
- plate || rail
- Rated Breaking Capacity:
- 800 A at 440 V for power circuit conforming to IEC 60947
- Flame Retardance:
- V1 conforming to UL 94
- Mechanical Robustness:
- shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz)
- Protective Treatment:
- TH 3)IEC 60068