Schneider Electric

Schneider Electric LC1D40004G6 IEC contactor, TeSys D, nonreversing, 60A resistive, 4 pole, 4 NO, 120VAC 60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D40004G6
MPN:
LC1D40004G6
Condition:
New
Circularity Profile:
N/A
Contactor Application:
resistive load
Operating Altitude:
9842.52 ft (3000 m) without derating
Minimum Switching Voltage:
17 V for control circuit
Control Circuit Voltage Limits:
0.3...0.6 Uc 60-60°C drop-out AC 50/60 Hz || 0.85...1.1 Uc 60-60°C operational AC 60 Hz
Protective Treatment:
THIEC 60068-2-30
Minimum Switching Current:
5 mA for control circuit
Flame Retardance:
V1 conforming to UL 94
Average Impedance:
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Fire Resistance:
850°C IEC 60695-2-1
Sustainable Offer Status:
Green Premium product
[Ue] Rated Operational Voltage:
power circuit 690 V AC 25...400 Hz
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
Mechanical Durability:
15000000 cycles
Compatibility Code:
LC1D
Overvoltage Category:
III
Ip Degree Of Protection:
IP2X VDE 0106
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Environmental Disclosure:
ENVPEP110205EN
Mercury Free:
Yes
Toxic Heavy Metal Free:
Yes
Control Circuit Type:
AC 60 Hz standard
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Connections - Terminals:
control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable
Coil Technology:
without built-in bidirectional peak limiting diode suppressor
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4
Product Certifications:
CSA || DNV || GL || BV || UL || CCC || RINA || LROS (Lloyds register of shipping) || UKCA
Tightening Torque:
control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw clamp terminal flat Ø 6 mm hexagonal || power circuit 5 N.m screw clamp terminal Philips No 2 hexagon
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for control circuit || 40 A (at 60°C) for power circuit
[Ie] Rated Operational Current:
60 A (at <60°C) at 440 V AC AC-1 for power circuit
Range Of Product:
TeSys Deca
Mounting Support:
plate || rail
Inrush Power In Va:
140-140 VA cos phi 0.75 (at 20°C)
Poles Description:
4P
Permissible Ambient Air Temperature Around The Device:
-5-60°C || -40-70°C at Uc
Device Short Name:
LC1D
Pole Contact Composition:
4 NO
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Maximum Operating Rate:
3600 cyc/h 60°C
Irms Rated Making Capacity:
140 A AC for control circuit conforming to IEC 60947-5-1 || 800 A at 440 V AC for power circuit conforming to IEC 60947
Country of Origin:
France
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Protective Cover:
with
Mechanical Robustness:
shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz)
Associated Fuse Rating:
10 A gG for control circuit conforming to IEC 60947-5-1 || 80 A at 690 V coordination type 1 for power circuit || 80 A at 690 V coordination type 2 for power circuit
Operating Time:
12...22 ms closing || 4...19 ms opening
Reach Free Of Svhc:
Yes
Insulation Resistance:
> 10 MOhm for control circuit
$609.60

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 60A resistive load rating. Contactor is supplied with a 120 VAC 60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 4.92 inches deep. It weighs 3.17 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose