Schneider Electric LC1D40008M7 IEC contactor, TeSys Deca, nonreversing, 60A resistive, 4 pole, 2 NO and 2 NC, 220VAC 50/60Hz coil, open style
Schneider Electric
$496.80
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 60A resistive load rating. Contactor is supplied with a 220 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 4.92 inches deep. It weighs 3.17 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Height:
- 127 mm
- Heat Dissipation:
- 4-5 W at 50/60 Hz
- Electrical Durability:
- 1.4 Mcycles 60 A AC-1 <= 440 V
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
- Rated Breaking Capacity:
- 800 A at 440 V for power circuit conforming to IEC 60947
- Utilisation Category:
- AC-1
- Protective Cover:
- without
- [Ith] Conventional Free Air Thermal Current:
- 60 A (at 60°C) for power circuit
- Weight:
- 1.44 kg
- [Icw] Rated Short-Time Withstand Current:
- 320 A 40°C - 10 s for power circuit || 720 A 40°C - 1 s for power circuit || 72 A 40°C - 10 min for power circuit || 165 A 40°C - 1 min for power circuit
- Power Dissipation Per Pole:
- 5.4 W AC-1
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Depth:
- 125 mm
- Irms Rated Making Capacity:
- 800 A at 440 V for power circuit conforming to IEC 60947
- Mounting Support:
- plate || rail
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Product Certifications:
- RINA || GL || UL || GOST || BV || LROS (Lloyds register of shipping) || DNV || CCC || CSA
- Protective Treatment:
- THIEC 60068-2-30
- Range:
- TeSys
- Average Impedance:
- 1.5 mOhm - Ith 60 A 50 Hz for power circuit
- Climatic Withstand:
- IACS E10 exposure to damp heat
- Toxic Heavy Metal Free:
- Yes
- Contactor Application:
- resistive load
- Associated Fuse Rating:
- 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
- Mercury Free:
- Yes
- Pole Contact Composition:
- 2 NO + 2 NC
- Fire Resistance:
- 850°C IEC 60695-2-1
- Net Weight:
- 1.44 kg
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ie] Rated Operational Current:
- 60 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Sustainable Offer Status:
- Green Premium product
- Range Of Product:
- TeSys Deca
- Device Short Name:
- LC1D
- Mechanical Robustness:
- shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz)
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Overvoltage Category:
- III
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Mechanical Durability:
- 6 Mcycles
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Coil Technology:
- without built-in suppressor module
- Reach Free Of Svhc:
- Yes
- Inrush Power In Va:
- 140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Warranty:
- 18 months